Sizing the surge-trol, Precise sizing for pump start-up, Precise sizing for pump shut-down – Amtrol SPT-28 User Manual

Page 3: Precise sizing example for pump shut-down based on

Advertising
background image

Description

Standard Construction

Shell

Steel

Bladder

Heavy Duty Butyl
NSF/ANSI 61

Bladder Thickness

.100 Minimum

System Connection Steel - ANSI Flange

Coating

Red Oxide Primer

Factory Precharge

25 PSIG (1.7 bar)

Use:

SG = Specific gravity of fluid:

Water 1

Ethylene glycol 1.1

Propylene glycol 1.1

Glycerin 1.3

Qs = Fire pump flow rate in gpm

Qss = Fire pump flow rate in feet per second

L

= Length of pipe in feet

a

= Speed of pressure wave

in feet per second:

Steel pipe 4500 ft/sec

Cast iron = 4500 ft/sec

Ductile iron 4500 ft/sec

PVC pipe = 1250 ft/sec

P

2

= Maximum allowable pressure

P

1

= Tank pre-charge pressure setting

n

= Gas constant (pre-charge gas) dry air 1.2

nitrogen 1.4

A = Area of Pipe - pipe size

V

= Velocity of water in feet per second

Precise Sizing For Pump Start-up:

Volume of Tank in Cubic Feet =

(

SG x 2 x Qs x L

) (

P

2

+ 14.7

)

1

/n

449a

P

1

+ 14.7

(

P

2

+ 14.7

)

1

/n

P

1

+ 14.7

-1

NOTE: Set pre-charge pressure 15% below static pressure.
NOTE: To convert cubic feet to gallons multiply by 7.481.

SIZING THE SURGE-TROL

Tank A

B

Sys.

C

D

E Ship

Vol. Height Diameter

Conn. Conn. Conn. Stand Wt.

Model

Inset CtrLine Dia

No.

Lit.

Gal

mm

ins.

mm

ins.

ins.

ins. ins.

ins.

kg

lbs.

SPT-7 200

53 1245 48

7

/

8

610

24

4

1

9

/

16

8

3

/

16

19 166 367

SPT-11 300

80 1600 62

7

/

8

610

24

4

1

9

/

16

8

3

/

16

19 208 459

SPT-14 400 106 1956 76

7

/

8

610

24

4

1

9

/

16

8

3

/

16

19 282 618

SPT-18 500 132 2311 90

7

/

8

610

24

4

1

9

/

16

8

3

/

16

19 333 731

SPT-21 600 158 1893 74

11

/

16

762

30

4

1

3

/

8

7

1

/

4

24 433 950

SPT-28 800 211 2365 93

1

/

8

762

30

4

1

3

/

8

7

1

/

4

24 513 1125

SPT-35 1000 264 2086 82

1

/

8

914

36

6

3

1

/

4

7

1

/

2

30 693 1520

SPT-42 1200 317 2465 94

1

/

2

914

36

6

3

1

/

4

7

1

/

2

30 784 1720

SPT-50 1400 370 2781 109

1

/

2

914

36

6

3

1

/

4

7

1

/

2

30 866 1900

SPT-56 1600 422 2178 85

3

/

4

1220 48

8

1

3

/

4

10

7

/

8

42 1049 2300

SPT-70 2000 528 2528 99

5

/

8

1220 48

8

1

3

/

4

10

7

/

8

42 1231 2700

Precise Sizing For Pump Shut-down:

Volume of Tank in Gallons = Vv

AF

AF - Acceptance Factor =

1 -

(

P

1

+ 14.7

)

1

/n

P

2

+ 14.7

Vv - Vacuum Volume = Qss x Tc x 7.481

Tc - Critical Time in seconds =

2L

a

NOTE: Set pre-charge pressure 50% below

static pressure.

Precise Sizing Example
For Pump Shut-down Based On:

Pump = 100 GPM
Pipe = 2” Steel Pipe; 1000 ft of pipe
Static Pressure = 100 psig
Max. Pressure = 150 psig
Pre-charge Gas = Dry Air

Tc =

2L = 2(1000) = 2000 = .444

a 4500 4500

Vv = Qss x Tc x 7.481 = 9.5 x .444 x 7.481 = 31.55

AF =

1 -

(

P

1

+ 14.7

)

1

/n =

1 -

(

64.7

)

1

/

1.2

= .54

P

2

+ 14.7

164.7

Volume of Tank in Gallons = Vv = 31.55 = 58.4

AF

.54

Recommendation = SPT-11