Operation, Steam or hot water preheating operation – AAON SA-070 User Manual

Page 47

Advertising
background image

47

Table 9 - R-410A Refrigerant Temperature-Pressure Chart

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

°F

PSIG

20

78.3

47

134.7

74

213.7

101

321.0

128

463.2

21

80.0

48

137.2

75

217.1

102

325.6

129

469.3

22

81.8

49

139.7

76

220.6

103

330.2

130

475.4

23

83.6

50

142.2

77

224.1

104

334.9

131

481.6

24

85.4

51

144.8

78

227.7

105

339.6

132

487.8

25

87.2

52

147.4

79

231.3

106

344.4

133

494.1

26

89.1

53

150.1

80

234.9

107

349.3

134

500.5

27

91.0

54

152.8

81

238.6

108

354.2

135

506.9

28

92.9

55

155.5

82

242.3

109

359.1

136

513.4

29

94.9

56

158.2

83

246.0

110

364.1

137

520.0

30

96.8

57

161.0

84

249.8

111

369.1

138

526.6

31

98.8

58

163.8

85

253.7

112

374.2

139

533.3

32

100.9

59

166.7

86

257.5

113

379.4

140

540.1

33

102.9

60

169.6

87

261.4

114

384.6

141

547.0

34

105.0

61

172.5

88

265.4

115

389.9

142

553.9

35

107.1

62

175.4

89

269.4

116

395.2

143

560.9

36

109.2

63

178.4

90

273.5

117

400.5

144

567.9

37

111.4

64

181.5

91

277.6

118

405.9

145

575.1

38

113.6

65

184.5

92

281.7

119

411.4

146

582.3

39

115.8

66

187.6

93

285.9

120

416.9

147

589.6

40

118.1

67

190.7

94

290.1

121

422.5

148

596.9

41

120.3

68

193.9

95

294.4

122

428.2

149

604.4

42

122.7

69

197.1

96

298.7

123

433.9

150

611.9

43

125.0

70

200.4

97

303.0

124

439.6

44

127.4

71

203.6

98

307.5

125

445.4

45

129.8

72

207.0

99

311.9

126

451.3

46

132.2

73

210.3

100

316.4

127

457.3


Operation


Unit operations should be controlled with
thermostat or unit controller, never at the
main power supply, except for emergency or
complete shutdown of the unit.

Steam or Hot Water Preheating
Operation
Valve control for steam and hot water
heating coils are by others. Heating is
accomplished by passing steam or hot water

through the steam or hot water coil
assembly.

Chilled Water or Non-Compressorized
DX Cooling Operation
Controls for chilled water cooling coil and
non-compressorized DX coil are by others.





Advertising