Service & Installation Clearances

Before setting the unit into place, caution must be
taken to provide clearance for unit panels/doors that
must be accessible for periodic service. These areas
contain the controls, safety devices, refrigerant, shut-
off valves and filter access.

HB package units have minimum service and airflow
clearance requirements.

Service Clearance Minimums:

- 36 inches to the front
- 10 inches to the back
- 20 inches to right and left ends

Airflow Clearance Minimums:

- 20 inches around the entire condenser intake

- 24 inches between condenser and obstructions
- 48 inches of clearance over the condenser air
discharge, and from adjacent condenser intakes




















































































48”

Wall or Obstruction

Condenser

Airflow

Minimum 20”

Clearance

RA

SA

Air In

Air In

Air In

Air Out

10”

Adjacent

Condenser

20”

Air In

HB Package Unit

Figure 12b, Airflow Clearance Minimums

Service Access Clearance

Air In

Air In

Air Out

36”

RA

SA

Air In

20”

20”

10”

Right

Left

Front

Back

Figure 12a, Service Clearance Minimums

Airflow to and from the condensing unit must not be
restricted. Obstruction to airflow will result in
decreased performance and efficiency. The
installation position must provide at least 20 inches
of condenser clearance for proper airflow into the
condenser coil. When the unit’s condenser is
positioned adjacent to another condenser, 48
inches of clearance is required between air intakes
for proper airflow and operation.

48”

Air Out

40”

Figure 12c, Other Airflow Clearance Minimums

Required condenser
clearance doubles to 40
inches in recessed areas

.

The HB package unit has a vertical air discharge.
There must be at least 48 inches of clearance
above the vertical air discharge. There must not be
any obstruction above the equipment that may
deflect discharge air back into the unit’s air inlets.
It is advisable to never place the unit directly under
an overhang. Condensing units should not be
installed in an enclosure or pit that is deeper than
the height of the unit. When the unit is installed in
a recessed area the coil side clearance is doubled
to 40 inches for inlet air.