TROUBLE

POSSIBLE CAUSE

ELECTRIC HEATING

SYSTEM OFF

1. Check power at line side of contactor(s).
2. Thermostat not set for heating.

1. Overload relay tripped.
2. Heater Relay not energized.
3. Blower Contactor not energized.
4. Capacitor shorted or open (PSC motors only).

1. Blower running backwards.
2. Dirty air filters.
3. Dirty coils.
4. Duct obstruction.
5. Belts loose.

1. One or more heater contactors are open.
2. Limit switches are open.
3. Heater relay open.
4. Heat strips burned out.

BLOWER DOESN'T DELIVER AIR

EVAPORATOR MOTOR WILL NOT RUN

BLOWER COMES ON, BUT LITTLE OR NO
HEAT

FAN MOTOR RUNS HOT AND CUTS OUT

1. Check power at lineside of contactor(s).
2. Thermostat not set for cooling.
3. High pressure control tripped.
4. Low pressure switch open (loss of charge).

1. Overload thermal protector open in motor.
2. Motor run capacitor open or shorted.
3. Motor failed.
4. Fan or shaft stuck.

1. Overload thermal protector open in motor.
2. Relay not closing.
3. Motor failed.
4. Capacitor shorted or open (PSC motors only).
5. Stuck shaft or blower wheel.

1. Check for low refrigeration charge.
2. Compressor overload setting.
3. Ambient temperature too low.
4. Filters dirty or air flow restricted.
5. Evaporator blower not running.

1. Line voltage too high.

1. Line voltage too low.
2. Limit switches are open.
3. Overload or pressure control tripped.

1. Blower running backwards.
2. Dirty filters.
3. Duct obstruction.
4. Belts loose.

SYSTEM OFF

BLOWER DOES NOT DELIVER AIR

COMPRESSOR WILL NOT START

COMPRESSOR SHORT CYCLES

EVAPORATOR BLOWER WILL NOT RUN

CONDENSER FAN WILL NOT RUN

COOLING PACKAGE

SERVICING, TROUBLE SHOOTING, INSPECTIONS & MAINTENANCE