STUCK COMPRESSOR

MOTOR WINDING OPEN

COMPRESSOR RUNS

REVERSE LEADS

CHECK UNIT FUSES

AND WINDING

GROUNDED WINDING

INTERNAL

OVERLOAD OPEN

REPLACE

COMPRESSOR

COMPRESSOR CHECKOUT PROCEDURE

NO POWER TO

CONTACTOR

POWER TO

UNIT

NO POWER TO

UNIT

COMPRESSOR

WON'T RUN

CHECK CIRCUIT BREAKER AT

POWER DISTRIBUTION PANEL

NO 24 VOLT POWER

TO HOLDING COIL

CONTACTOR

OPEN

POWER TO HOLDING COIL

HOLDING COIL BURNED OUT

REPLACE CONTACTOR

BROKEN OR LOOSE CONTROL

TRANSFORMER OPEN

COMPRESSOR LOW AMBIENT LOCKOUT OPEN

(TEMPERATURE OUTSIDE BELOW 55 DEG.)

HI PRESSURE SWITCH OPEN

LO PRESSURE SWITCH OPEN

THERMOSTAT NOT CALLING FOR COOLING

CONTROL PANEL NOT SET FOR COOLING

COMPRESSOR

DOESN'T RUN

REPLACE

COMPRESSOR

REPLACE

COMPRESSOR

MOTOR

WINDING OPEN

POWER TO

COMPRESSOR

ALL 3 LEGS

COMPRESSOR

DOESN'T HUM

IF COMPRESSOR DOME IS HOT,

IT MAY BE LOCKED OUT ON

INTERNAL OVERLOAD.

WAIT FOR RESET, IT COULD TAKE

AS LONG AS 2 HOURS.

REPLACE LEADS

BROKEN LEADS

NO POWER TO
COMPRESSOR

COMPRESSOR

HUMS

CONTACTOR

CLOSED

POWER TO CONTACTOR

ALL 3 LEGS

LOW AIR (CONDENSER)

OVERCHARGE OF REFRIGERANT

AIR IN SYSTEM

DIRTY CONDENSER COIL

HIGH HEAD
PRESSURE

LOW HEAD

HIGH SUCTION

PRESSURE

DEFECTIVE COMPRESSOR VALVES

LOW AIR (EVAPORATOR)

LOW REFRIGERANT CHARGE

LOW

SUCTION

PRESSURE

RESTRICTED FEEDER TUBE

BAD EXPANSION VALVE POWER ELEMENT

REPLACE COMPRESSOR

CHECK FILTERS,

OR DIRTY EVAPORATOR COIL

OR LOOSE BELT

COMPRESSOR RUNS

OR

COMPRESSOR CYCLES

(Poor Cooling)

CHECK COMPRESSOR

ROTATIONAL

DIRECTION