Stage (marked "lo") and the second one for 2, Stage (marked "hi"), Set the unit on high fire and adjust the 2 – Allied Air Enterprises Upflow User Manual

Page 20: Stage low fire, then adjust the 1, Stage) and 3.5" w.c. (2, Stage) and 10.0" w.c. (2

Advertising
background image

The gas control (Figure 13) has two separate

pressure regulator adjustment screws, one for 1

st

stage

(marked "LO") and the second one for 2

nd

stage (marked

"HI").

The adjusting screws are positioned on either

side of the barbed fitting. The pressure regulator
adjustment is sensitive: one turn of the adjusting
screw will result in a relatively large change in
manifold pressure. Turn regulator-adjusting screws
IN (clockwise) to increase pressure, OUT
(counterclockwise) to decrease presure.

Set the unit on high fire and adjust the 2

nd

stage high

fire pressure regulator to the required setting. Disconnect
the violet wire from the "HI" terminal on the gas control
and the burners will drop down to the 1

st

stage low fire,

then adjust the 1

st

stage pressure regulator setting as

required. Gas input must never exceed the value shown
on the furnace rating label. These units are equipped for
rated input at manifold pressures of 2.3" w.c. (1

st

stage)

and 3.5" w.c. (2

nd

stage) for natural gas. When these

furnaces have been converted for use with LP (propane)
gas, the manifold pressures are 6.4" w.c. (1

st

stage) and

10.0" w.c. (2

nd

stage). After proper adjustments,

reconnect violet wire and furnace should go up to 2

nd

stage high fire. Turn OFF gas, replace manifold pressure
tap pipe plug, regulator adjustment vent cap, and turn ON
gas.

At higher altitudes and varying heating valves,
manifold pressure or orifice changes maybe
required. Consult Tables 7 and 8 for appropriate
values. Failure to follow this warning could lead to
a hazardous furnace operating condition and result
in serious bodily injury or loss of life.

Determining Furnace Input - Natural Gas Only

NOTE:

All access doors must be in place when checking
gas input.

1. Turn OFF all other gas appliances (except for pilot

burners) served by the same gas meter.

2. With furnace operating in full heat cycle, note how

many seconds it takes for one full revolution of the
smallest dial on the meter. Typically, this will be a
1/2 - or - 1 - cubic foot test dial.

3. Using the number of seconds for one revolution and

the size of the meter dial, determine the cubic foot
per hour of gas flow by using the formula provided
below or Table 5.

Cubic Ft/Hr =

Number of Dial Revolutions x Cubic Foot/Revolution x 3600
Time (in seconds) Required for Number of Timed Revolutions

TABLE 5

Gas Rate (Cubic Feet per Hour)

Seconds for

One

Revolution

TEST DIAL

1/2

Cubic

Feet

1

Cubic

Foot

2

Cubic

Feet

10

160

360

720

12

150

300

600

14

129

257

514

16

113

225

450

18

100

200

400

20

90

180

360

22

82

164

325

24

75

150

300

26

69

138

276

28

64

129

258

30

60

120

240

32

56

113

226

34

53

106

212

Seconds for

One

Revolution

TEST DIAL

1/2

Cubic

Feet

1

Cubic

Foot

2

Cubic

Feet

36

50

100

200

38

47

95

190

40

45

90

180

42

43

86

172

44

41

82

164

46

39

78

156

48

37

75

150

50

36

72

144

52

35

69

138

54

34

67

134

56

32

64

128

58

31

62

124

60

30

60

120

4. Calculate the furnace input using the following

formula:

BTUH = Cubic Ft/Hr x BTU/Cubic Foot

The local gas supplier should be able to provide the
heating value of the gas, in BTU/cubic foot. If a
specific value is not available, use 1000 BTU/cubic
foot for Natural gas or 2500 BTU/cubic foot for
Propane (LP).

Furnace input should be maintained within ± 2% of
the value on the rating plate or appropriate altitude
derate. Adjust manifold pressure or change
orifices size if required.

5. Calculate the unit's actual input rate.

Example:

If the heating value of the natural gas is 1015
Btu/cu. and it takes 60 seconds to burn 2 cu.
ft. of gas then:

Input = 1015 Btu/cu. ft. X 1 rev X 2 cu. ft./rev. X 3600

60 sec.

Input = 121,800 Btu/hr.