Safety Instructions

DANGER!

Risk of explosion!
To avoid the risk of explosion, follow not only the safety instructions in the respective
operating instructions, but also observe the following information concerning
operation in the hazardous area:

• Observe the specifications relating to temperature class and ambient temperature

on the rating plate.

• Do not use the devices with gases or dust which have a lower ignition temperature than

specified on the rating plate.

• Installation, operation and maintenance may be performed by qualified technicians only.
• Observe the applicable safety regulations (also national safety regulations) as well as the

general regulations of technology concerning installation and operation.

• Do not repair the device yourself, but replace it with an equivalent device. Repairs may be

performed by the manufacturer only.

• Do not expose the device to mechanical and/or thermal stresses which exceed the limits

described in the operating instructions.

To avoid the risk of explosion, observe the following information when performing
installation and maintenance in the hazardous area:

• Do not open the housing of the device when hazardouse atmosphere exist.
• To avoid an electrostatic charge, wipe the housing surface with a damp cloth only.
• Secure cable connections which have circular connectors with suitable securing clips.

For example: EXCLIP, FA. Phoenix Contact, type SAC-M12-EXCLIP-M, art. no. 1558988

or type SAC-M12-EXCLIP-F, art. no. 1558991.

• Use only cable and line entries which are authorized for the particular application area and

are screwed together according to the appropriate installation instructions.

• If the cable gland is pre-assembled, install it according to the installation instructions

supplied by the manufacturer of the screw connection.

Before start-up, check whether the cable gland was installed in the hazardous area as

described in the appropriate installation instructions.

• Seal all cable glands which are not required with ex-approved screw plugs.
• Do not open the housing of the device for operating inside switches when hazardous

atmosphere exist.

While bringing into sevice no hazardous atmosphere shall exist.

• Lock the cover with a torque of 10 Nm.
• Field installation with restriction at the installation site: protected installation position.

Select an installation site which excludes an increased mechanical load at the installation

location.