Start-up and operation of the
position controller Type 8692

OUT ANALOG.-.Configuration.of.the.analogue.output

Only for the versions:

• one analogue output

• one analogue and two binary outputs

The feedback signal of the current position (

POS) or of the set-point value (CMD) can be transmitted to the control

centre via the analogue output.

SELEC

OUT POS

EXIT

OUT type

Output of the current position

OUT ANALOG

ENTER

OUT CMD

ENTER

Output of the set-point value

SELEC

4 - 20 mA

Selection of
the unit signal

EXIT

0 - 20 mA

0 - 10 V

0 - 5 V

Figure 69:

Operating structure OUTPUT-ANALOGUE

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

OUT BIN1.-.Configuration.of.the.binary.output.1

OUT BIN2.-.Configuration.of.the.binary.output.2

The following description is valid for both binary outputs

OUT BIN 1 and OUT BIN 2, as the operation in the menu

is identical.

The binary outputs 1 and 2 can be used for one of the following outputs:

• Alarm output for excessively large control deviations of the position controller

• for the output of the current position with respect to a specified limit position (> or <)

• for the output: actuator in safety position

• for the output: sensor break

• for the output: operating state (AUTOMATIC / MANUAL)