English, Configuration – Burkert Type 1066 User Manual

Page 28

Advertising
background image

26 - 1066

I

NSTALLATION

AND

C

OMMISSIONING

english

Network topology of a DeviceNet system

Line with a main line (trunk line) and several drop lines.
The main line and the drop lines are made up from identical material (see sketch).

ATTENTION!

To avoid reflections, fit terminating resistors at both ends of the trunk line (120

).

Configuration

8 DIP switches are fitted for the configuration:

• DIP switches 1 to 6 for the DeviceNet addresses
• DIP switches 7 and 8 for the baud rate

DIP switch

Setting the DeviceNet address

MAC ID – Medium Access Control Identifier:

[Example of value allocation at switch DIP1:
DIP 1=off=0 / DIP 1=on=1 / MAC ID=DIP 1*2

0

+DIP 2*2

1

+...+DIP 6*2

5

]

NOTE

Before the commissioning of the controller with DeviceNet, the

EDS-Datei must be read

into DeviceNet Configuration Tool. The required files (BUE1066.EDS and BUE1066.ICO)
are available on diskette or over the Internet.

DI P 1

[ 2

0

=1]

DI P 2

[ 2

1

=2]

DIP 3

[2

2

=4]

DI P 4

[ 2

3

=8]

DIP 5

[ 2

4

=16]

DI P 6

[ 2

5

=32]

MAC

ID

off

of f

off

of f

off

of f

0

on

of f

off

of f

off

of f

1

off

on

off

of f

off

of f

2

.. .

. . .

.. .

. ..

.. .

. ..

.. .

off

on

on

on

on

on

62

on

on

on

on

on

on

63