Step 2: Connect external position indicator

Gently pull the cover of the standard position indicator

out of the housing cover (see

Fig. 2: ).

Close housing cover

note!

Display element may be damaged if the housing
cover is closed carelessly.
When the external position feedback is installed, ensure
that the housing cover is not shifted or damaged when
closing the display element.

When closing the housing cover, lift it slightly to pre-

vent it from touching the display element.

Place the external position indicator in the round recess

of the housing cover and press down until it engages
(see

Fig. 2: ) .

Installation is now complete.
Next connect the external position feedback to the power
supply, as described in the following chapter.

english

13

External position
indicator

Cover
for standard
display element

Housing cover

Fig. 2:

Connecting external position indicator

english

14

elecTrical connecTion

8.

Proximity switch 1

Proximity switch 2

1

4

3

2

Fig. 3:

Electrical connection

english

15

Pin Configu-

ration

External circuit / signal level

1 Supply

10 ... 30 V

+10 V ... +30 V

1 10 ... 30 V

2 Switching

output (NO)
Proximity
switch 1

+10 V ... +30 V

2 Open /

10 ... 30 V

3 GND

GND

3 GND

4 Switching

output
(NO)
Proximity
switch 2

+10 V ... +30 V

4 Open /

10 ... 30 V

Electrical connection

Tab. 1: