Burkert Type S030 User Manual

Page 10

Advertising
background image

36

Install the fitting on the pipe to comply with the
upstream and downstream distances defined by
standard EN ISO 5167-1 (see Fig. 3).

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows

at 90°

Pipe with 2 elbows at 90°

in 3 dimensions

Pipe with 1 elbow at 90°

or 1 T-piece

With pipe expansion

With pipe

reduction

Fig. 3: Upstream and downstream distances depending

on the design of the pipes.

English

37

Use a flow conditioner, if necessary, to obtain the best
accuracy.

Prevent the formation of air bubbles in the pipe (see
Fig. 4).

Ensure the pipe is always filled with liquid (see Fig. 5).

Correct

Correct

Incorrect

Incorrect

Direction of fluid flow

Fig. 4: Additional recommendations on installation

English

37

38

Correct

Incorrect

Correct

Incorrect

Fig. 5: Additional recommendations on installation

English

39

installing a fitting with weld ends

Follow the previously described general installation
recommendations.

note

the seal on the fitting with weld-end connections
may be damaged during welding.

Before welding the weld-ends, unscrew the 4 tigh-
tening screws.

Remove the sensor holder.

Remove the seal.

Weld the weld-ends.

After welding, correctly replace the seal in the
groove.

Replace the sensor holder.

Tighten the 4 screws in an alternating pattern, app-
lying a nominal tightening torque of 1,5 Nm.

English

39

Advertising