Burkert Type SE56 User Manual

Page 13

Advertising
background image

TECHNICAL MANUAL

Rev.

Pagine

13/52

Filling By

Checked By

03

PROFIBUS DP MODULE- DATA LINK

DESCRIPTION

Document Data

Date

Date

File name

ProfibusDP_emanual_Burkert_04.doc

19/03/08 19/03/08 19/03/08


13

The connectors must allow these connections.

Parameter

DP, Cable type A

Surge impedance in Ω

135...165 for a frequency of 3...20 MHz

Effective capacitance (pF/m)

≤ 30

Loop resistance ( Ω/km)

≤ 110

Core design (solid)

AWG 22/1

Core design (flexible)

> 0,32 mm²

The table shows the cable parameters for PROFIBUS copper signal cables with RS-485 transmission

standard.

2. CYCLIC DATA EXCHANGE

With the Cyclic Service of data exchange the slave return Dynamic Data that include measurement

values which are continuously changing e.g. Flow rate, totalizers, etc..

The module support five type of configurations with is possible sets the better combination of type of

information of the Flow meter.
The type of Configuration is set in the file GSD.

Below there are the description of the possible types of configuration with the realtive structure of data:

2.1. FIRST CONFIGURATION: 8 BYTE INPUT

Below there is a description of the contents of each byte:

bytes 0-3:

(32 bit single precision IEEE floating point, MSB first) Flow rate in % or Flow rate in t.u. or

(32 bit long integer, MSB first) totalizer for TOTAL or PARTIAL volume + or - or batch quantity

(see section 2.2 Data Type)

bytes 4-5: (16 bit unsigned integer, MSB first) process flags:
bit 0 =1 if the excitation is too fast for the sensor connected

bit 1 =1 if the maximum alarm is active

bit 2 =1 if the minimum alarm is active

bit 3 =1 if the Flow rate exceeds the scale range value (overflow)

bit 4 =1 if one or more output impulses are saturated (too many impulses to emit)
bit 5 =1 if the measurement signal is highly disturbed or if the sensor is disconnected

bit 6 =1 if the measurement tube is empty

bit 7 =1 if the circuit powering the coils is not working or the sensor is disconnected

bit 8 =1 if the second measurement scale is active

bit 9 =1 if the Flow rate is lower than the cut-off threshold

bit10=1 if the Flow rate is negative
bit11=1 if a new measurement value calculated for the display is available

bit12=1 if the counter block signal is active

bit13=1 if dosing is in progress

bit14=1 if a calibration cycle is in progress

bit15=1 if a Flow rate simulation is in progress

byte 6: (8 bits integer) measurement dynamic variation as a %

byte 7: (8 bits integer) Data Type ( see section 2.2 Data Type )

NOTE: The values in the “32 bits single precision IEEE floating point” format are floating point numbers

which can be represented during writing by any decimal digits. To keep the same numerical format visible