Burkert Type SE56 User Manual

Page 22

Advertising
background image

TECHNICAL MANUAL

Rev.

Pagine

22/52

Filling By

Checked By

03

PROFIBUS DP MODULE- DATA LINK

DESCRIPTION

Document Data

Date

Date

File name

ProfibusDP_emanual_Burkert_04.doc

19/03/08 19/03/08 19/03/08


22

bit 0 =1 if DPC31 B

byte 6: (8 bits integer) MAC State Offline / Passive Idle
bit 0 =1 if the MAC is in Passive Idle

byte 7: (8 bits integer) watchdog state
bit 0-1 = 00 --> Baud Search
01

-->

Baud

Control

10

-->

DP_Control

byte 8: (8 bits integer) baud rate
bit 0-3 = 0000 --> 12 MBd
0001

-->

6

MBd

0010

-->

3 MBd

0011

-->

1.5

MBd

0100

-->

500 kBd

0101

-->

187.5

kBd

0110

-->

93.75

kBd

0111

-->

45.45

kBd

1000

-->

19.2 kBd

1001

-->

9.6

kBd

byte 9: (8 bits integer) DP state machine


bit 0-1 = 11 --> Data_Exchange

INDEX Input = 33(dec) Internal Data

byte 0: (8 bits integer) current INDEX Input

byte 1: (8 bits integer) current INDEX Output
byte 2: (8 bits integer) slave software version (major number)

byte 3: (8 bits integer) slave software version (minor number)

byte 4-9: (8 bits integer) device name («ML 210», «ML M3F»)

byte 10: (8 bits integer) Flow meter software version (major number)

byte 11: (8 bits integer) Flow meter software version (minor number)

byte 12-13: (8 bits integer) (16 bits unsigned integer, byte 13=MSB):hardware / software enabling flags,
bit 0 = LSB, bit 15 = MSB:

Bit

s

Funzioni ML 210/M3F

0-2 current access level (0..7)
3

channel 1 impulses in use

4

channel 2 impulses in use

5

channel 1 frequency in use

6

channel 2 frequency in use

7

scale range 2 in use