Burkert Type 8070 User Manual

Page 4

Advertising
background image

12

4-20 mA output

• Accuracy
• Min. voltage drop at

the device terminals

• Loop impedance

• +/- 1,5% of the full scale
• < 10 V at 20 mA

• max. 100 W at 12 VDC,

max. 700 W at 24 VDC, max.
1000 W at 30 VDC

NPN/PNP output

open collector, 50 mA max.
current, frequency up to 600 Hz

Power consumption

< 200 mW

English

13

7

assemBly, insTallaTion

7.1 assembly of Type 8022

note!

For the fault-free operation of the Type 8022 observe
the following during installation:
• When screwing to the sensor, ensure the seal is seated

correctly.

▶ Torque the screw to a value between 0.2 and 0.3 Nm,

in order not to damage the housing. With a damaged

housing, correct operation cannot be guaranteed.

Fig. 1 shows how Type 8022 is screwed to the sensor.

English

14

Fig. 1:

Installing Type 8022 on the sensor

English

15

7.2 electrical installation

The electrical connection of the device is made on a terminal
strip via cable gland, or an M12 male fixed connector.

Terminal
assignment
1

NPN

2

PNP

3

12 - 30 V DC

4

GND

Fig. 2:

Terminal assignment, version with cable gland

Pin assignment
1

12 - 30 V DC

2

NPN

3

GND

4

PNP

Fig. 3:

Pin assignment, M12 male fixed connector

English

Advertising
This manual is related to the following products: