Installation of the fitting onto the pipe – Burkert Type 8020 User Manual

Page 7

Advertising
background image

24

Warning

risk of injury due to non-conforming commissioning.
Non-conforming commissioning may lead to injuries and
damage the device and its surroundings.
• Before commissioning, make sure that the staff in

charge have read and fully understood the contents of

the manual.

• In particular, observe the safety recommendations and

intended use.

• The device / the installation must only be commis-

sioned by suitably trained staff.

note

risk of damage to the device due to the environment
• Protect this device against electromagnetic interfer-

ence, ultraviolet rays and, when installed outdoors, the

effects of the climatic conditions.

To make sure the device operates correctly, plug in
and tighten the connector.

English

25

installation of the fitting onto the
pipe

Choose a fitting appropriate to the velocity and the
flow rate of the fluid inside the pipe, refer to the graphs
at right (see Tab. 3). The graph is used to determine
the DN of the pipe and the fitting appropriate to the
application, according to the fluid velocity and the flow
rate.

Install the fitting on the pipe as described in the oper-
ating instructions of the fitting used.

English

25

26

Tab. 3:

Diagram flow/ fluid velocity/ DN of S020 fitting

0.1

0.3 0.5 1

3 5 10

0.01

0.02

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

m

3

/h

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

2000

3000

l/min

0.3 0.5 1

3 5 10

30

m/s

fps

US gpm

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

DN 65

DN 50 (DN65)*

DN 40 (DN50)*
DN 32 (DN40)*
DN 25 (DN32)*

DN 20 (DN25)*

500

1000

2000

2000

5000

10000

5000

20000

5000

10000

20000

30000

50000

100000

DN 400

DN 350

DN 300

DN 250

DN 200

DN 150

DN 125
DN 100

DN 80

Flow rate

Fluid velocity

Example

1)

English

27

Example:
• Specification:

- nominal flow: 10 m

3

/h,

- optimal flow velocity: between 2 and 3 m/s

• Solution: intersection between flow rate and flow velocity

in the graph gives the appropriate pipe diameter, DN40
(or DN50 for the asterisked fittings).

* For the fittings:
• with external thread connections acc. to SMS 1145,
• with welding end connections acc. to SMS 3008,

BS 4825 / ASME BPE or DIN 11850 Rg 2,

• Clamp connections acc. to SMS 3017/ ISO 2852, BS

4825 / ASME BPE or DIN 32676

1)

The device cannot be installed on the DN20 fittings listed

above.

English

27

Advertising