St100 hart common practice commands – Fluid Components International ST100 Series HART User Manual

Page 18

Advertising
background image

ST100 Series HART

14

Fluid Components International LLC

ST100 HART Common Practice Commands

The ST100 HART supports Common Practice commands 35, 38, 40, 42, 44, 45, 46, 48, 50, and 51.

HART COMM NUMB.

HART COMMAND DESCRIPTION

HART DATA TYPE & SIZE

35

WRITE PV RANGE VALUES

RNG UNITS CODE

UNSIGN (1BYTE)

UPPER RANGE VALUE

UPPER-RNG VAL

FLOAT (4 BYTES)

LOWER RANGE VALUE

LOWER-RANGE VALUE

FLOAT (4 BYTES)

38

RESET "CONFIGURATION CHANGE" FLAG

RESET CONFIG. CHANGE. FLAG

UNSIGN (1BYTE)

40

ENTER/EXIT FIXED CURRENT MODE (IN mA)

I MODE SELECT

Value =0 means exit fixed current mode

FLOAT (4 BYTES)

42

PERFORM DEVICE RESET

RESET INSTRUM.

UNSIGN (1BYTE)

44

WRITE PV UNITS

PV UNITS CODE

ENUM (1BYTE)

45

TRIM DAC ZERO - MEASURED CURRENT CHAN #1 IN

(mA)

TRIM_DAC_ZERO

FLOAT (4 BYTES)

46

TRIM DAC GAIN - MEASURED CURRENT CHAN #1 IN

(mA)

TRIM_DAC_GAIN

FLOAT (4 BYTES)

48

READ ADDITIONAL DEVICE STATUS

25 BYTES

DEVICE-SPECIFIC STATUS

6 BYTES

EXTENDED DEVICE STATUS

1 BYTE

DEVICE OPERATING MODE

1 BYTE

STANDARIZED STATUS 0

1 BYTE

STANDARIZED STATUS 1

1 BYTE

ANALOG CHAN SATURATED

1 BYTE

STANDARIZED STATUS 2

1 BYTE