Technical Specifications: DLR Series

All prices and specifications are subject to change without notice.

Technical Description

Description

The DLR Series is designed with a single low-pressure high-intensity UV lamp centered
inside a protective quartz sleeve. The disinfection chamber is either 304 or 316L stainless
steel and is electro-polished with male NPT Inlet/Outlet. The UV lamp and quartz jacket
assembly are easily removable from one side of the disinfection chamber.

UV disinfection chamber

• Material: stainless steel electro-polished

• UV sensor

• Mounting: vertical or horizontal

• Inlet/Outlet connections: Male NPT thread

• Mounting brackets included

UV lamp

High output low pressure UV lamp

Control Box

• Material: ABS, designed for wall or UV chamber mounting

• Electronic power supply (ballast)

• LED readout

• Solenoid valve activator outlet

• Cable length UV chamber/control box: 4.9’

Application

The DLR series is engineered to disinfect clear fresh water to meet drinking water
standards.

Operational capacity

Clear fresh water up to 30 US GPM

Options

• Voltages 120 Volt /60 Hz (CE conforming)

• Solenoid inlet valve (NPT size corresponding to reactor NPT connection for each unit)

¾”, 1”, and 1 ½” normally closed.

Flow Rate Table: Valid for water with minimum UV transmittance > 90% @ 1cm (254nm)

DLR Series type

1

2

4

7

Flow rate (gpm) at UV dose of 40 mJ/cm

2

at the end of lamp lifetime*

4 10 18 30

Flow rate (gpm) at UV dose of 30 mJ/cm

2

at the end of lamp lifetime**

5 13 24 40

*

40 mJ/cm

2

= 40,000 µWs/cm

2

** 30 mJ/cm

2

= 30,000 µWs/cm

2

Notes: (1) Flow rates subject to final bioassay results

(2) Flow rate for UV Dose 30 calculated based on NSF certified flow at 40 mJ/cm

2

(3) Flow rates based on flow restrictor installed in line.

UV Reactor, Stainless Steel 304 (1.4301) Electro-polished

Reactor connections, male NPT thread

½”

¾”

¾”

1”

Width (inches)

3.54 3.54 5

5

Height (inches)

18.5 26.38 26.38 40.55

Diameter (inches)

2.76 2.76 4.02 4.02

Weight (lb.) approx.

3.75

5.29

7.06

11.03

Operating pressure (psi) max.

125

125

125

125

Pressure loss (psi) approx.

2

2

2

2

UV Lamp, Low Pressure High Output

Lamp Type

NLR1825 WS NLR1845 WS NLR1845 WS NLR1880 WS

Lamp Power (Watt)

16.5

40

40

84

UV-C Output at 254 nm, new lamp (Watt)

5.5

14

14

25

Quantity

1 1 1 1

Lamp

lifetime

(days)

365 365 365 365

21