Parameterization and operation

4.5

2-channel RTC103 N-Module parameterization on the sc1000 controller

In addition to the 1-channel version, there is also a 2-channel
version that can control two activated sludge tanks. The relevant
parameters therefore appear twice and are identified as channel
1 and channel 2.

MODBUS

ADDRESS

Start address of an RTC within the MODBUS network.

DATA ORDER

Specifies the register order within a double word. Presetting:
NORMAL

DATALOG INTRVAL

Indicates the interval in which the data is saved in the log file.

[min]

PROGNOSYS

Activate or deactivate PROGNOSYS for RTC control. "Activate"
means if Measurement Indicator from relevant sensor decrease to
50% or lower RTC control do not use this measurement and switch
to adequate fall back strategy.

SET DEFAULTS

Restores the factory settings.

MAINTENANCE

RTC DATA

RTC MEASUREMEN

Specifies the value measured by the RTC, e. g. the influent
measurement.

RTC ACTUAT VAR

Specifies the variable calculated by the RTC, e. g. whether the
aeration should be switched on or off.

DIAG/TEST

EEPROM

Hardware test

RTC COMM TO

Communication time-out

RTC CRC

Communication check sum

MODBUS ADDRESS

Here, the address is displayed where the communication actually
takes place. Presetting: 41

LOCATION

Here, a location name can be assigned for better identification of the
RTC module, e.g. activation 2.

SOFT-VERSION

Shows the software version of the RTC communication card
(YAB117) in the sc1000.

RTC MODE

Shows the installed RTC module variant, e.g. 1-channel closed-loop
control.

RTC VERSION

Shows the software version of the RTC module.

4.4.3

1-Channel RTC103 N-Module VFD (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES

RTC