2 setup and configuration, 1 load cell (transducer) terminals, 2 power supply terminals – Cleveland Motion Controls Classic Series DIN Rail Amplifier with Isolated Output MWI-13467 REV CA User Manual

Page 10: 3 output terminals, Etup and, Onfiguration, Ransducer, Erminals, Ower, Upply

Advertising
background image

C

LASSIC

S

ERIES

A

MPLIFIER W

/

I

SOLATED

O

UTPUTS

MAN-13467

REV

CA

Page 10 of 30

2 S

ETUP AND

C

ONFIGURATION

2.1 L

OAD

C

ELL

(T

RANSDUCER

)

T

ERMINALS

Input

Terminal

Function

Description

Notes

J1-1 EXC

RET

Supply return for bridge
excitation

Zero voltage terminal for
transducers

COMMON

J1-2 -INPUT

Load cell signal from
transducer 1

Low going output from
transducer

10K ohm line-to-line

J1-3 +INPUT

Load cell signal from
transducer 2

High going output from
transducer

J1-4 +V

EXC

Bridge excitation source for
transducers

5.0 Volt or 10.0 Volt supply
terminal,

max. load 100 mA

J1-5

N.C.

NO CONNECTION

Make no connection

J1-6

N.C.

NO CONNECTION

Make no connection

J1-7

N.C.

NO CONNECTION

Make no connection

J1-8 SHLD

DRN

Cable shield
drain terminal

Cable Shield for –INPUT and
+INPUT transducer cables

Connect only at amplifier


Transducers (load cells) use strain gages, which have limited insulation levels to ground (earth).
This requires that the COM terminals be connected to ground (earth) to prevent damage to the
transducers (load cells).



2.2 P

OWER

S

UPPLY

T

ERMINALS

Supply

Terminal

Function

Description

Notes

J2-1

24V RET

Power Supply

Power supply return

Must not exceed 50 volts
from P.E.

J2-2

+24 VDC

Power Supply

Positive supply source

+20 to +28 VDC
@ 180 mA max


A fuse with a rating of 0.38A must be used in the 24 VDC supply lead to limit potential
damage to the amplifier in the event of circuit malfunction.


2.3 O

UTPUT

T

ERMINALS

Output

Terminal

Function

Description

Notes

J2-3

COMMON

Output signal return


Common for +/- 10V and
+/-2V output

J2-4

+/- 10V OUT

Voltage Output signal

Undamped bi-polar
tension signal

Max. load 2 mA

J2-5

mA MTR RET

mA meter signal

Used for current format meter
return

Current through 1 mA
meter returns here

J2-6 METER

OUT Output

signal

Damped bi-polar tension
signal

Switchable 2.0 V F.S.
or 1 mA F.S.

J2-7 4-20

mA

OUT

Current loop Output
signal

Undamped tension signal
current loop source

Internal loop supply

J2-8

4-20mA RET

Output current signal

Current return for 4-20 mA
loop

At –15 VDC with respect to
common