CCU Hardware Reference

Theory of Operation

CTI Products, Inc.

68-11843-105

8

3.6

Section 5 – TX Normal / ECS Select

The Tx Normal / ECS Select section has a similar Toggle function as the
Main/Standby function.

There are three external inputs:

/Tx Toggle 1 (from Console 1)

/Tx Toggle 2 (from Console 2)

/Tx Toggle 3 (from Console 3)


There are four logic outputs:

/Tx Normal Select 1

(Normal)

/Tx Normal Select 2

(Normal)

/Tx ECS Select 1

(Inverted)

To TX ECS Select Relay

/Tx ECS Select 2

(Inverted)

To Console Input


The TX ECS select can be used to disable the comparator repeat function. See
details in Section 2 - Repeater Control.

3.6.1

Slaved TX Select

The TX Normal / ECS Select section can be forced to be controlled by Section 4 -
Rx Normal / ECS Select as shown below:

Option

Switch


Up


Down

1

Slave Mode:
TX Normal / ECS Select
controlled by the
Rx Normal / ECS Section

Independent Mode:
TX Normal / ECS Select
operates independently from the
Rx Normal / ECS Section

Table 3 – Slaved TX Select

If the Slaved mode is used, the Toggle inputs to the TX section are not connected.

3.7

Section 6 – TSAM Force Select Output

When one of the Toggle sections (typically the TX Main/Standby) is used to
control the TX Select (TXS1 & TXS2) inputs on the TSAM Transmitter Steering
Unit, the TSAM requires an additional Force Select input. Section 6 provides a
square wave output with a period of about 1 Hz. This ensures that the TSAM's
outputs will switch within 1 second of the output change in the CCU.

The Force Select output is not fed back to the MCNRCD network, since it would
only add a lot of unnecessary channel traffic.