Remote ptt cib connections, Remote cor cib connections, Emote – CTI Products OTAL On-the-Air Driver Assembly User Manual

Page 10: Onnections

Advertising
background image

CTI Products, Inc.

OTAL Driver Assembly User Guide

R

EMOTE

PTT

CIB

C

ONNECTIONS

Remote PTT signals are connected to J1 on a remote CIB. (See Figure 1.) PTT inputs are not required if COR
Only OTAL Logic is used.

Remote PTT signals shall be either:

ƒ Isolated Form A Relay Contacts (or opto-isolated relay outputs)

closed when PTT signal is present.

ƒ Logic Outputs - Negative Ground, Active Low when PTT is active.

They must be capable of:

ƒ Up to +20 VDC Open Circuit

ƒ Sinking a minimum of 30 mA when active

ƒ Maximum of 0.2 V when active

Signals must not drive other equipment.

The Remote PTT signals appear on the following pins of J1 of the remote PTT CIB module as follows:

Remote PTT CIB J1

Wire Color

CIB Function

OTAL System Function

1 Blu/Wht

Ground

Ground-Common

22

Org/Vio

Rx 1

PTT 1B input

47

Vio/Org

Rx 2

PTT 2B input

16

Blu/Yel

Rx 3

PTT 3B input

41

Yel/Blu

Rx 4

PTT 4B input

10

Slt/Red

Rx 5

PTT 5B input

35

Red/Slt

Rx 6

PTT 6B input

4

Brn/Wht

Rx 7

PTT 7B input

29

Wht/Brn

Rx 8

PTT 8B input

The “B” suffix on the PTT signals indicates the Remote PTT.

R

EMOTE

COR

CIB

C

ONNECTIONS

The Remote COR signals are connected to J1 on a remote CIB. (See Figure 1.)

Remote COR signals shall be either:

ƒ Isolated Form A Relay Contacts (or opto-isolated relay outputs)

closed when a carrier is detected.

ƒ Logic Outputs - Negative Ground, Active Low when a carrier is active.

They must be capable of:

ƒ Up to +20 VDC Open Circuit

ƒ Sinking a minimum of 30 mA when active

ƒ Maximum of 0.2 V when active

Signals must not drive other equipment.

Field

Connections

10