CTI Products NCB/EM with External PSTN Modem User Manual

Page 51

Advertising
background image

CTI Products, Inc.

NCB-EM User Guide

Appendix E. Troubleshooting

45

Table E5

If the ACT LED (on local

NCB) . . .

REASON

CORRECTIVE ACTION

Occasionally blinks on, then

off.

Normal operation indicating a message

packet has passed through the router
module of the NCB.

Go to next Table.

Does not illluminate when

“RSVC” button on remote
NCB is pressed.

1. LonWorks Service Pin message from

remote NCB is not reaching the remote
modem.





2. LonWorks Service Pin message from

remote NCB is not reaching the local
modem.

3. LonWorks Service Pin message from

remote NCB is not reaching the local
NCB.

4. LonWorks Service Pin message from

remote NCB is not passing through the
local router module.

1a. Verify that “ACT” and “ERR” LED’s

on remote NCB flash once. If not,
return remote unit for
evaluation/repair.

b. Verify that “CD” LED is illuminated

on the local and remote modems. (See
above)

c. Verify that “SD” LED briefly

illuminates on remote modem when
the “RSVC” button is pressed on
remote NCB.

d. If ‘1c’ is not ok, check serial cable

connection between remote NCB and
modem.

2.

Verify that “RD” LED briefly
illuminates on local modem when the
“RSVC” button is pressed on remote
NCB.

3.

Check serial cable connection between
the local NCB and modem.

4a. Place the remote router in Repeater

mode and verify that the local “ACT”
LED illuminates when “RSVC” button
on remote NCB is pressed.

b. If ‘4a’ is ok, re-commission the local

NCB router.

c. If ‘4a’ is not ok, swap either the local

or remote unit with a known-good-unit
to determine the faulty unit.

Does not illuminate when

local LonWorks nodes are
transmitting messages.

1. LonWorks message packets from local

nodes are not passing through the local
router module.

1a. Verify the connection between the

local LonWorks nodes and the local
NCB.

b. Place the local router in Repeater mode

and verify that its “ACT” LED
illuminates when local LonWorks
nodes are transmitting messages.

c. If ‘1b’ is ok, re-Commission the local

NCB.

d. If ‘1b’ is not ok, return the local NCB

unit for evaluation/repair.

Table E5 continued on next page

Advertising