CTI Products NCB/EM with External PSTN Modem User Manual

Page 60

Advertising
background image

CTI Products, Inc.

NCB-EM User Guide

Appendix H. Ring Mode

54

Connection and Enabling Procedure

The following steps should be followed when installing a series of NCB modules for Ring Mode operation:

1) Connect all NCB modules in default mode (Ring Mode disabled).

a) During installation of each NCB, enable both NCB serial ports using the appropriate “BAUD” and

“MODE” settings for switches on the rear panel.

b) Then press the “RESET” button on the front panel. (The front panel “ERR” LED will blink

rapidly if both serial ports are not terminated at another functioning device.)

2) Be certain that the ring is open in one place. It is usually convenient to remove the cable from one of

the serial “PORT” connectors on the rear of the NCB, leaving the other one connected.

3) From the Central Site, with all Remote Site NCB’s communicating, set Ring Mode parameters and

enable Ring Mode on the Remote Site NCB’s.

a) Begin by enabling Ring Mode for the NCB located just before the ring opening. (This will be the

furthest NCB around the ring, even though it may be very near the Central Site.)
Once Ring Mode has been enabled for an NCB, it will not communicate with other NCB’s in the
ring until all are enabled for Ring Mode.

i)

If the LonMaker for Windows browser is being used to enable Ring Mode (using the
configuration property UCPT_RingMode), a message may appear: “WARNING WHILE
DOWNLOADING CP’S TO DEVICE”. This is understandable, since communication with
other units in the ring is discontinued until all units are enabled for Ring Mode. Since
communication is discontinued, the device shape representing the Control Neuron on the
LonMaker drawing will indicate a “Node Error”.

ii) If the NCB/Plug plug-in is being used to enable Ring Mode, NCB/Plug will automatically

close, since communications to that NCB is no longer possible until all remaining NCB’s are
set to Ring Mode.

b) Enable Ring Mode for the next closest NCB around the ring. Finish by enabling Ring Mode for

the NCB at the Central Site.

4) Close the ring.

Communication is now possible and the device shapes representing the Control Neurons of each
NCB on the LonMaker drawing will indicate “Node Normal”.

Disabling Procedure

The following steps should be followed when disabling Ring Mode operation for a series of NCB modules:

1) Open the ring by removing the cable from one of the serial “PORT” connectors on the rear of the NCB

at the Central Site.

2) With all Remote Site NCB’s communicating, disable Ring Mode on the Remote Site NCB’s:

a) Begin by disabling Ring Mode for the NCB located just before the ring opening. (This will be the

furthest NCB around the ring, even though it may be very near the Central Site.)
Once Ring Mode has been disabled for an NCB, it will not communicate with other NCB’s in the
ring until all are disabled for Ring Mode.

b) Disable ring mode for the next closest NCB around the ring. Finish by disabling ring mode for the

NCB at the Central Site.

To prevent the “ERR” LED from continually blinking, disable any NCB serial “PORT” no longer in use, using
the appropriate “BAUD” and “MODE” settings for switches on the rear panel. Then press the “RESET” button
on the front panel.