Advanced controller programming, Entering advanced programming mode, Maximum run time – Controlled Products Systems Group HSLG-111 User Manual

Page 15: Single button input setup, Stagger mode, Stagger delay time

Advertising
background image

HSLG Slide Gate Operator Installation Guide

- 13 -

P1220 Revision X8 6-22-2011

Advanced Controller Programming

Entering Advanced Programming Mode

To access and program the Advanced Programming functions, for each
programming session, Advanced Programming must be enabled.

After exiting programming, the Advanced Programming functions
will be available on the programming display during the next
programming session unless the operator has run 50 or more
cycles. After that, Advanced Programming must be enabled again.

Maximum Run Time

The factory default for the Maximum Run Time (MRT) is 99 seconds.
When the operator starts, a timer will begin counting. If a open or close
limit is not reached or an obstacle or reversing input is not received
before the timer expires, the operator will stop, the unit locks out and the
alarm sounds. The timer can be set for 10 to 99 seconds, but should be
left at 99 in most applications. Setting it too close to the actual run time
may cause the time to expire with changing ambient temperature, gate
conditions, etc…

If AC is present and an open or close limit is not reached or an obstacle
or reversing input is not received before this timer exceeds MRT, the
operator will stop, the unit locks out and the alarm sounds.

Single Button Input Setup

This function is used for selecting the operation for single button controls
and radio receivers.

The factory default sets the SINGLE input terminal so successive inputs
will cycle the operator in OPEN-STOP-CLOSE-STOP order.

Alternately, the SINGLE input can be set to cause the gate to OPEN
unless the gate is fully open. If the gate is fully open, the input will cause
the gate to CLOSE.

Stagger Mode

(Rarely used in slide gate installations)

This function is used in dual gate installations only. The factory
default sets the Stagger Mode to OFF. In dual gate installations the two
operators communicate through the 3-wire COMM LINK interface. When
using the Stagger Mode, set one operator for delayed opening and the
other operator for delayed closing. The Stagger Delay Time programming
function (see below) sets the length of the delay.

NOTE: This function will only be displayed if dual gate operation is

selected.

Stagger Delay Time

(Rarely used in slide gate installations)

This function is used in dual gate installations only. The factory
default sets the Stagger Time to 0 seconds (OFF). The Stagger Time
sets the delay for the Stagger Mode. The Stagger Time can be set from
1-99 seconds.

NOTE: This function will only be displayed if dual gate operation is

selected.

FUNCTION

ADVANCED PROGRAMMING FUNCTIONS
WILL NOT BE DISPLAYED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

ADVANCED

PROGRAMMING

"AD"

ADVANCED PROGRAMMING OPTIONS
WILL BE DISPLAYED

NOTE: ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER
EXITING PROGRAMMING UNTIL
THE GATE CYCLES 50 TIMES

FUNCTION

SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR

SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

SINGLE BUTTON

INPUT SETUP

"SB"

FUNCTION

SETS THIS OPERATOR FOR
DELAYED OPEN

DISABLES STAGGER FUNCTION

SETS THIS OPERATOR FOR
DELAYED CLOSE

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

STAGGER

MODE

"SM"

DUAL GATES

ONLY

FUNCTION

PRESS ENTER FOR 1 SECOND

WHILE DISPLAY IS FLASHING, PRESS
UP OR DOWN TO CHANGE THE
MAXIMUM RUN TIME (10-99 SECONDS)

OPTIONS

MAXIMUM RUN

TIMER

DISPLAY SHOWS CURRENT
MAXIMUM RUN TIME SETTING

ENTER

ENTER

PRESS ENTER TO STORE THE VALUE

"RT"

FUNCTION

SET STAGGER DELAY VALUE
1 TO 99 SECONDS

STAGGER TIMER DISABLED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

STAGGER

DELAY TIME

"ST"

DUAL GATES

ONLY

Advertising
This manual is related to the following products: