Advanced controller programming (cont.), Auxiliary relay mode, Reverse delay time – Controlled Products Systems Group HSLG-111 User Manual

Page 16: Brake delay time, Constant pressure mode, Shadow loop open prevention

Advertising
background image

HSLG Slide Gate Operator Installation Guide

- 14 -

P1220 Revision X8 6-22-2011

Advanced Controller Programming (Cont.)

Auxiliary Relay Mode

The Auxiliary Relay has normally open and normally closed contacts.
The factory setting disables the Auxiliary Relay. The relay can be set for:

• Maglock: To deactivate a magnetic or solenoid gate lock, the relay

will energize during any pending or actual gate motion (open only).

• M4: To deactivate a magnetic or solenoid gate lock, the relay will

energize during any pending or actual gate motion (open only).
3 seconds after the gate starts to move, the relay will de-energize.
This option is used for higher current solenoid locks.

• Ticket

Dispenser: The relay will energize while the gate is moving

in the open direction and at the full open limit, or in an entrapment
condition.

• Strobe: To activate a warning strobe light, the relay will energize

during any pending or actual gate motion (either open or close).

• Alarm: The relay will energize if the gate is manually forced open

from the full closed position.

Reverse Delay Time

The factory default sets the Reverse Delay to 1 second. The operator
will wait the length of the delay before reversing direction. This feature
will not change the reversal time when the operator is responding to an
entrapment condition from an obstruction input or inherent entrapment
protection sensor. The Reverse Delay can be set from 1 to 9 seconds.
Heaver gates require a longer delay to allow time for the gate to stop.

Brake Delay Time

The factory default sets the Brake Delay to no delay (0 seconds). Heavy
gates may require delayed braking to allow the gate to slow down before
stopping it. The operator can be set to wait the length of the delay after
running before applying the brake. The Brake Delay can be set from
0 to 3 seconds.

Constant Pressure Mode

The factory default allows momentary pressure on a control station’s
OPEN or CLOSE button to cycle the operator. The controller can be set
to require constant pressure on the OPEN, CLOSE, or both buttons to
run the operator.

NOTE: If a button is set for constant pressure, and it is released

before the operator reaches the open or close limit, the operator will
stop the gate at its current position.

Shadow Loop Open Prevention

If the shadow loop is triggered, it always prevents the gate from closing if
the Auto Close Timer activates or a CLOSE command is given while the
gate is at the full open position.

The controller can also be set to prevent the gate from opening if the
shadow loop is triggered while the gate is at the close limit position. This
prevents a swing gate from opening into a vehicle if it’s parked near the
gate on the inside.

FUNCTION

SET TIMER VALUE
1 TO 9 SECONDS

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

REVERSE

DELAY TIME

"RD"

FUNCTION

SET TIMER VALUE
0 TO 3 SECONDS

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

BRAKE

DELAY TIME

"BD"

FUNCTION

AUXILIARY RELAY USED FOR
MAGLOCK CONTROL

AUXILIARY RELAY DISABLED

AUXILIARY RELAY USED FOR
TICKET DISPENSER CONTROL

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

AUXILIARY

RELAY MODE

"AR"

AUXILIARY RELAY USED FOR
WARNING STROBE LIGHT

AUXILIARY RELAY USED FOR
CONNECTION TO ALARM DEVICE

AUXILIARY RELAY USED FOR
MAGLOCK OR SOLENOID CONTROL
3 SECOND DELAY TO RE-ENERGIZE

FUNCTION

CONSTANT PRESSURE SET TO OFF
(MOMENTARY PRESSURE ON)

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

CONSTANT

PRESSURE MODE

"CP"

OPEN BUTTON SET FOR
CONSTANT PRESSURE

CLOSE BUTTON SET FOR
CONSTANT PRESSURE

OPEN AND CLOSE BUTTONS BOTH SET
FOR CONSTANT PRESSURE

FUNCTION

STANDARD OPERATION
SHADOW LOOP INHIBITS CLOSING ONLY

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

SHADOW LOOP

OPEN PREVENTION

"SP"

OPEN INHIBIT ON, SHADOW LOOP INHIBITS
OPENING AND CLOSING

Advertising
This manual is related to the following products: