RAM 50 GB

15

RAMSET

www.ramsetinc.com

JP9 - Input Power:

1,2) 24 VAC power.

Connection from external transformer to

power Control Board.

JP3 - 3 Button:

1) Open 2) Stop 3) Close 4) Common

Used with a 3-button station to open,

stop, and close the gate. The open and close are
normally open connections and the stop is a nor-
mally closed connection, remove jumper wire when
connecting 3 button station. Common and stop are
also used with a photo eye used to protect the
backplane of the operators.

1) 24 VDC.

5) Relay Common

2) 24 VAC

6) Fully Closed-N.C.

3) 5 VDC

7-8) Constant/Prewarn

4) Fully Open-N.O.

9-10) E.R.D. Alarm.

If E.R.D. is triggered twice before reaching a limit,

24 VDC is supplied to sound an alarm (included with
operator).

JP2 - Relay Connections:

JP7 - Master/Slave plug:

1) A 2) B 3) Common

Used to synchronize the operation be-

tween two gates. A three-wire, Shielded cable is
needed to run from the A, B, & Common (jP7) of
the master P.C.B. to the A, B, & Common (jP7) of
the slave P.C.B.

JP10 - Loop Inputs:

1-2) Reverse 3-4) Exit 5-6) Phantom

Use with ILD-24s, Loop wires should

be connected to this plug.

JP4, JP5 & JP8 - Reverse, Exit & Phantom

Sensor:

Used with the Ramset ILD-24 plug-in loop

detector. The Loop wires should be connected into
the “LOOP INPUTS” plug.

Fully Open N.O. (works with relay common)-

Relay rated at 125 VAC, 2 amps. Normally open con-
nection. Open contact occurs until the open limit is
triggered. When the open limit is triggered, a closed
contact occurs.

Relay Common -

Relay rated at 125 VAC, 2 amps.

The common of the Fully Closed N.C. relay and the
Fully Open N.O. relay.

Fully Closed N.C. (works with relay common)

Relay rated at 125 VAC, 2 amps. Normally closed
connection. Closed contact occurs until the closed
limit is triggered. When the closed limit is triggered, an
open contact occurs.

WIRE BOARD CONNECTIONS

JP11 - Foot Pedal Plug:

Stops the motor from running while

the foot pedal is engaged.