Controlled Products Systems Group DTEK110VAC User Manual

Page 2

Advertising
background image

Front Indicators

1. Green Led is ON - the detector is powered.
2. Red Led is ON - the detector detected a vehicle
3. Green Led is Blinking - the loop failed and is shorted or disconnected
4. Green Led is Blinking with two consecutive fast blinks - the loop failed in the past and
now is working correctly.
5. Red Led is Blinking at the start of a vehicle detection - the Filter function is ON
6. Red Led is Blinking at the end of a vehicle detection - the Extend function is ON
7. Red Led is Blinking during a vehicle detection - 4 minute limited presence time has
expired.
Note: Functions on pins 6 and 10 are reversed if DIP 4 is set to OFF

Front Controls

Reset

This toggle switch when pushed momentarily down will reset the detector

Frequency Counter

This toggle switch when pushed momentarily up will count the frequency
on the loop. This count is displayed by the Red Led blinks, each blink
represents frequency of 10K Hz. Count between 3 to 13 blinks confirms
that the loop detector is tuned to the loop.

Frequency

This toggle switch controls the loop frequency. Set different frequencies
on adjacent loops. Verify frequencies with the frequency counter by
counting the Red Led blinks.

Back Controls

Sensitivity

This rotary switch controls the detector sensitivity. During normal
operation the sensitivity level is set to 3 or 4.

DIP Switch Functions

3 seconds

Extend detect

8

6 seconds

Extend detect

7

Automatic Sensitivity Boost On

ASB Off

6

Filter On

Filter Off

5

"Fail Safe"

"Fail Secure"

4

4 minute limited presence time

Constant presence

3

Pulse on Un-detect

Pulse on detect

2

Presence on Relay II

Pulse on Relay II

1

ON

OFF

DIP

When Dip 7 and 8 are in ON position the extend time is 9 seconds.

DTEK.lwp Created: March 23, 1998 Revised: January 16, 2003 10:44AM Pages:5