Installation and Wiring

6

AXB-232++ RS-232/422/485 Interface

Wiring Devices to the AXB-232++

Preparing captive wires

To connect the wiring into a captive-wire connector:

1.

Strip 1/4 inch off the wire insulation for all four wires.

2.

Tin 2/3 of the exposed wire.

3.

Insert each wire into the appropriate captive-wire connector up to the insulation.

4.

Tighten the captive screws to secure the fit in the connector.

Wiring guidelines

The interface requires a 12 VDC power to operate properly. The interface uses a PSN2.8 power

supply. The Central Controller supplies power via the AXlink cable or external 12 VDC power

supply. The maximum wiring distance between the Central Controller and interface is determined

by power consumption, supplied voltage, and the wire gauge used for the cable. The table below

lists wire sizes and maximum lengths allowable between the AXB-RS232++ and Central

Controller. The maximum wiring lengths for using AXlink power are based on a minimum of 13.5

volts available at the Central Controller’s power supply.

Using AXlink

Connect the AXlink wiring to the connector on the AXB-232++ as shown in FIG. 4.

Using AXlink and External Power Supply

Connect the AXlink and power wiring to the connector on the AXB-232++ as shown in FIG. 5.

If the device is using a separate power supply, do not connect the power wiring from
the AXB-232++ to that device.

Wiring Guidelines at 160 mA

Wire Size

Maximum Wiring Length

18 AWG

733.57 feet (223.59 m)

20 AWG

464.11 feet (141.46 m)

22 AWG

289.35 feet (88.19 m)

24 AWG

182.39 feet (55.59 m)

FIG. 4 AXlink bus and +12 VDC power wiring

FIG. 5 AXlink bus and +12 VDC power wiring

PWR
AXP
AXM
GND

AXlink

System

PWR
AXP
AXM
GND

PWR
AXP
AXM
GND

+12 VDC
GND

AXlink

System

Power Supply

PWR
AXP
AXM
GND