Communication – Liquid Controls SP4000 User Manual
Page 92
89
SP4000 Flow Computer
2
RATE
1
TOTAL
Enter Maximum Block Size. Data transmissions are first partitioned
into 128 character blocks. Up to the recommended maximum number
of blocks can be sent in each transmission. Smaller block counts are
more likely to be sent successfully than larger block counts. 3 is
recommended for preliminary block size.
Input:
number from 0 to 15
Display:
3
MAX BLOCK SIZE
Select YES or NO for Initialize Pager prompt. Select YES and press
ENTER to locally initialize the pager once installation has been
completed. A message will indicate if initialization is successful.
Initialize Pager before attempting to register pager.
Selection:
YES, NO
Display:
YES
INITIALIZE PAGER
MAX BLOCK SIZE
(Pager)
INITIALIZE PAGER
(Pager)
COMMUNICATION
6.13
COMMUNICATION
(Continued)