AB-0602A ARCHITECTURAL BALLAST DRIVER

Version 0.10 OWNERS MANUAL 07/05/2012

www.lightronics.com

Lightronics

Inc.

509

Central

Drive

Virginia

Beach,

Va

234354

757

486

3588

DESCRIPTION AND FEATURES

The AB-0602A is a 6 circuit, 2400 Watts per circuit
ballast driver intended for dimmable fluorescent and
LED fixtures which use a switched 120VAC hot
feed and dimmed 120VAC control signal to operate
them. A three circuit version (AB-0302A) is also
available and operates identically.

The AB-0602A can also be used as a conventional
relay pack by using only the switched hot feed
controls without the dimmed 120VAC signal.

EXTERNAL CONTROLS

The AB-0602A can communicate with remotely
located control equipment in several ways.

A USITT DMX-512 protocol bus is provided so the
unit may be used with any DMX lighting console.
The AB-0602A is fully patchable with respect to the
DMX bus.

The AB-0602A may also be controlled by several
types of wall mounted smart remote stations. Smart
remotes communicate with the unit by way of a low
voltage RS-485 bus. This bus is completely separate
from the DMX bus. Smart remotes are used to
activate preset scenes which have been stored in the
AB-0602A. There are several types of smart remote
stations. Multiple smart remotes of the same or
different types may be chained together on the RS-
485 bus. The same RS-485 bus may be chained to
multiple AB-0602A units.

The AB-0602A may additionally be controlled by an
arrangement of one or more momentary switches
(simple remotes). The switches may be used to
control a specific set of eight scenes which are
stored in the AB-0602A.

INSTALLATION

PHYSICAL LOCATION

The unit is intended for

INDOOR USE ONLY

and

should not be subjected to excessive moisture or
heat. The AB-0602A is designed to be wall
mounted in a equipment room or electrical
distribution area.. The ambient air in the installation
area should be below 86 deg F. Provide spacing

between the unit and other equipment to allow air
flow around the unit. See the

DIMENSIONS AND

LOCATIONS

diagram for more location information.

POWER REQUIREMENTS











TURN OFF ALL POWER SOURCES BEFORE
MAKING CONNECTIONS

The internal AB-0602A circuitry requires a 120VAC
line feed. The circuitry is fused with a 1/2 Amp fast
acting 1 1/4" x 1/4", 250V fuse.

LINE IN CONNECTIONS

A separate 120 VAC line in feed is needed for each
of the loads (A - F). The maximum current for each
feed circuit is 20 Amps. The diagram

DIMENSIONS

AND LOCATIONS

shows the connection details. A

grounding bar is also provided.

SWITCHED HOTS CONNECTIONS

Switched hot connections are made on a terminal
strip inside the AB-0602A. The diagram

DIMENSIONS AND LOCATIONS

shows the

connection details.

DIMMED HOT OUTPUT CONNECTIONS

Dimmed hot connections are made on a terminal
strip inside the AB-0602A. The maximum load is 1
Amp. per circuit. The diagram

DIMENSIONS AND

LOCATIONS

shows the connection details.

CONTROL SIGNAL CONNECTIONS

Connectors with screw down terminals are provided
for connection to DMX consoles, smart remotes, and
simple remote stations. Specific wiring connection
information for all external control signals is shown
in the

CONTROL SIGNAL CONNECTIONS

diagram

.

DANGER