ADC AD-115ES User Manual

Page 28

Advertising
background image

24

American Dryer Corp.

113202 - 10

A 1/8” N.P.T. plugged tap, accessible for a test gauge connection, must be installed in the main gas supply
line immediately upstream of each dryer.

IMPORTANT: Pipe joint compounds that resist the action of natural and liquid propane (L.P.) gases

must be used.

IMPORTANT: Test ALL connections for leaks by brushing on a soapy water solution (liquid

detergent works well).

WARNING: NEVER TEST FOR GAS LEAKS WITH A FLAME!!!

IMPORTANT: The dryer and its individual shutoff valve must be disconnected from the gas supply

piping system during any pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).

NOTE: The dryer must be isolated from the gas supply piping system by closing its individual manual

shutoff valve during any pressure testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa).

Advertising