Zero Adjustment: R52 (276-515/276-525) R64 (276-517/276-527) Adjust the output current
to 4.000mA with zero flow through the Flowmeter.

Span Adjustment: S1 Coarse Range and R35 or R47 Fine Span Adjustment. Table I lists the
approximate volumetric displacements of flow meters that can be used with the 276
transmitters. Use this table to calculate the RPM of the flow meter at maximum flow.

TABLE I.

METER MAXIMUM FLOW AND DISPLACEMENT

FLOWMETER

MAXIMUM FLOW

DISPLACEMENT PER REVOLUTION

CC/MIN

GAL/MIN

CC

GALLONS

213

1,800

0.48

0.870

.00023

214

10,000

2.64

10.5

.00285

215

40,000

10.6

47.6

.0128

216

100,000

26.4

169.5

.0446

220

10,000

2.64

9.12

.0024

221

55,000

14.5

23.5

.0062

222

75,000

19.8

47.4

.0125

241

189,000

50.0

62.1

.0164

251

189,000

50.0

62.1

.0164

242

540,000

143.0

182.0

.0480

243

1,400,000

370.0

574.0

.152

244

3,500,000

925.0

1700.0

.456

245

8,000,000

2114.0

6060.0

1.60

(FOR EXAMPLE: THE 213 MAX RPM IS: 1800 CC/MIN ÷ 0.870 CC/REV = 2069 RPM.)

Table II lists the RPM range of each Range Switch setting for both 276 transmitters. Use this
table to estimate the correct range position.

TABLE II.

RPM RANGE VS SWITCH POSITION (RPM AT 20mA OUT)

2 7 6 - 5 X 5

2 7 6 - 5 X 7

SWITCH

MAX

MIN

MAX

MIN

POSITION

GAIN

GAIN

GAIN

GAIN

1

1294

3620

1290

3612

2

568

1589

549

1537

3

249

697

233.6

654

4

109

306

99.4

278.3

5

48

134

42.3

118.4

6

21

59

18

50.4

276-515-350 © 2006 Max Machinery, Inc.

( 7 )

USER OPTIONS & ADJUSTMENTS

—Zero & Span Adjustments