Transmitters calibrated at the factory with a flow meter are shipped with a calibration sheet

and will not require further adjustment. Transmitters shipped alone will have to be phased to

the flow meter and wet calibrated.

Grounding Switches: S2-1: This switch connects circuit common to the transmitter case

through two back to back 15 µF @ 20V capacitors. S2-2: This switch connects common and

case ground directly together.

By using either S2-1 or S2-2 the effects of electrical noise on the transmitter can be reduced.

Excessive electrical noise can result in a zero offset of the output signal and a reduction of

accuracy. It is good practice to have a circuit directly connected to ground at one point. This

will probably be at the indicator or receiving end of the signal.

By activating S2-1, electrical noise between the case and the circuitry of the transmitter can

be considerably reduced, without causing ground loop problems. If the system is not ground-

ed at the indicator or if the flow meter is not physically grounded through its plumbing, use

S2-2. To activate either switch, depress the side of the switch that is numbered.

272-500-350 © 1996 (Rev. 8/00) Max Machinery, Inc.

Page 7

USER OPTIONS AND ADJUSTMENTS

Amphenol Connectors (See above) are use on Transmitter Models 272-5X5, 5X7 & 5X8.