MaxPower Corp GE VH Series User Manual

Page 2

Advertising
background image

Modifications reserved

Page 2/5

TDS_VHE_XXX_0K7_2K0_XGB.doc

Technical Data Sheets VH700-2000VA UL

General data

Topology

VFI, on line double conversion

Nominal output rating

VA/W

700/630

1000/900 1500/1350

1920/1740

Overall efficiency at nominal load

%

>87

Heat dissipation at inverter nominal load,

PF=0.9. and charged battery

W

86

123

184

237

Cooling air (77-86ºF)

CFM

15

21

32

41

Audible noise level at one meter

dB(A)

< 45 dB(A), load and temperature dependent

Operating temperature range

32 to 104ºF (0 to +40ºC) 59-77 ºF recommended for batteries)

Storage temperature range

-4 to 122ºF (-20ºC to +50ºC)

Relative humidity Max.

20-95% (non-condensing)

Protection degree

Steel-plastic / IP20

Safety

UL 1778, 4

th

Edition

EMC

FCC Part-15, Class B

Surge capacity

EN61000-4-5: 6kV line-line / 6kV line-earth

Electrostatic discharge immunity

EN 61000-4-2, 4kV contact / 15kV air discharge

Transport

On pallet / Tower and rack mountable

Colour

RAL 9005 (black)

Outlet connectors

NEMA 5-20R ( additional L5-20R in 2000 VA )

Inlet connectors

IEC-C14 in 700-1000VA and C20 in 1500-2000VA

Cooling

Forced air

Input converter (rectifier + power factor correction)

Nominal AC input voltage

120V

Input frequency range

45 - 66 Hz

Power factor

> 0.99

THDi

< 6%

Nominal input current (no charging, U

in

= nominal) Adc

6.6

9.1

13.9

16

Inrush current

None

DC output voltage

2 x 210V

Battery charger

Battery charging characteristic

Constant current charging until boost voltage, then float
voltage charging

AC input voltage range

60 to 140V

DC output voltage

Vdc

40.5

81

Output current limitation

Adc

1.5

Recharge time

3 hours for 90% capacity, standard battery

Battery data

Battery type

Sealed lead acid, VRLA

Float voltage at 25°C

Vdc

40.5

81

Number & rating of 12V batteries (standard version)

3*7Ah

3*9Ah

6*7Ah

6*9Ah

Standard backup time at nominal resistive load

min

8

8

7.2

8

End of discharging voltage (Vdc/cell)

Vdc

1.66

Standard backup extensions (Table.1 for backup
time)

NO

YES

YES

YES

Advertising