Technical specifications, Typical configuration – MaxPower Corp Powerware Expansion Chassis User Manual

Page 2

Advertising
background image

RS-485

(SNMP)

Invensys Powerware Division
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
or 919.872.3020
Fax: 1.800.753.9433
www.powerware.com

Europe
Finland: 358 94 52 661
France: 33 1 6012 7400
Germany: 49 721 961790
Italy: 39 02 6600661 2
UK: 44 (0) 1753 608700

Southeast Asia
Singapore: 65 6861 0377

China and North Asia
Hong Kong: 852 2745 6682

Japan
Shinagawa, Tokyo: 81 3 3447 4441

Australia and South Pacific
Sydney, Australia: 61 29878 5000

Canada
Toronto, Ontario: 416.798.0112

Brazil
Sao Paulo, Brazil: 55 11 3845
4369/ 55 11 3704 3632

Mexico
Col. Napoles, Mexico:
525.488.3333

SFT26FXA

Revision 3/02
Reprint 3/02

Technical Specifications

Part Number

05147063

Description

Adds Modbus Card plus 2 additional slots for X-slot communication cards to supported UPSs

Included Card

Modbus Card

Optional Cards

ConnectUPS-X SNMP/Web Adapter

ConnectUPS-M SNMP Module

Single Port Serial Card

Multi-Server Card

Additional Modbus Card

Communication with UPS

DB-9 via included serial cable

UPS Compatibility

Powerware 5115

Powerware 5125

Powerware 9120

Powerware 9125

Powerware 9170+

Powerware Prestige 9

Powerware Plus 12, 18, 36

Powerware 9315 Reverse Transfer Module

Powerware 9315 Hot Sync Parallel Redundant Module

Powerware 9315 Hot Sync Parallel Capacity UPM

Powerware 9315 Hot Sync Parallel Capacity SBM

Mounting

Stand-alone (feet), rack (19 inches), or wall mount

Operating Temperature

10º to 40ºC

Operating Humidity

20 to 80% relative humidity (non-condensing)

Power Input

Switchable 230/120 VAC, 50/60 Hz (via included transformer)

Power Consumption

6 Watts maximum

Dimensions

18" x 1.75" x 6"

Weight

6 lbs. (including 1 lb. for power supply)

Regulatory

FCC Class B

Modbus is a registered trademark of Modicon. Powerware, X-slot and ConnectUPS are trademarks of Powerware Corporation.

OR*

Typical Configuration

Multi-Server Card

Building Management System

Network Management System

OR

(HTTP)

Web Browser

Servers running LanSafe for graceful shutdown

*Cards can be used in either slot.

(Modbus)

RS-232

ETHERNET

POWER

ConnectUPS SNMP

Web Card

Ethernet Gateway

Power Meter

PLC