3.4 Altering a Datapoint

The following procedure illustrates how to enter EMODE and use the configuration function to alter the
contents of datapoint B000 (B0) with a 97. Entering a 97 in B00 invokes the display test which strobes the
display matrix dots on and off at 5 second intervals (approximate). When off, a perimeter of dots still remains
lit. Figures 3-11 and 3-12 are display test illustrations that support the procedure provided in Table 3-3. It
should be noted that EMODE has a 20 second timeout if it is accessed and its functions (e.g., configure or
display) are not used.

Table 3-3. Procedures to Display a Datapoint

Step

Press

Once

Shift

Result

Press to

Locate

Target

Char.

Result

1

MODE

Puts instrument in engineering mode.

2

If CONFIGURE appears instead of DISPLAY, press F2.

3

F3

Displays entry line: POINT .
(If the prompt KEY? appears, see Table 3-5.)

4

B

Puts B on entry line: POINT .B.

5

.BΔ

0

Shifts B and puts 0 on entry line: POINT .B0.

6

.B0Δ

0

Shifts B0 and puts 0 on entry line: POINT .B00.

7

F3

Displays contents of B00 (0).

8

Hold

.

locator

B00 contents shifted right; only locator point
remains on the entry line: B00 .

9

9

Puts 9 on entry line: B00 .9.

10

.9Δ

7

Shifts 9 and puts 7 on entry line: B00 .97.

11

F3

Enters 97 in B00 to start the display test.

12

To stop test, change B00 contents from 97 to 00 (Instrument Suspend State).

13

MODE

Returns instrument to operator mode.