33 auto/manual switch 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller FLEXIBLE CONTROL STRATEGIES User Manual

Page 54

Advertising
background image

2.7.33 AUTO/MANUAL SWITCH 2

The Auto/Manual Switch 2 (AMS 2) module provides a continuous output signal that is derived
from one of three sources which are the output track value (OTV), control output auto value (CO),
or the manual push button value. The output priority is OTV, CO, and output push buttons. The in-
put variable parameter values also affect the output, as determined by the output selection made.
The two tables that follow list the input variables and the parameters. As shown in the third table,
two logical output signals, L153 and L155, indicate which source is supplying the continuous out-
put signal at C174. An illustration of the AMS 2 module follows the tables.

Inputs

Inputs

WIRELIST

SYMBOL

DATA

TYPE

ASSIGNED VALUE

WIRELIST

SYMBOL

DATA

TYPE

ASSIGNED VALUE

B219

AE2

L

B221

OTV2

C

B220

SWOVT2

L

B222

CO2

C

Output Datapoints: C174, L153, L155

Parameters

Parameters

SYMBOL

DATAPOINT

ASSIGNED VALUE

SYMBOL

DATAPOINT

ASSIGNED VALUE

SWA2

L160

HML2

L170

OTE2

L167

OH2

C181

T3-2

C190

OL2

C182

L155

L153

C174 OUTPUT

0

0

Output push button value.

1

0

Control Output auto value - CO (when SWA = 1 and AE = 1, AUT is true - lower toggle to 1). CO out.

0

1

Output Track Value - OTV (when SWOVT = 0, and OTE = 1, OVTS is true - upper toggle to 1). OTV
out.

1

1

Output Track Value - OTV (same as above, but both toggles at 1).

AE2...auto enable
A/M2...auto/manual
AUT2...auto status
CO2...control output
HML2...hard manual limit
OH2...output high limit
OL2...output low limit
OTE2...output track enable
OTV2...output track value
OUT2...output
OVTS2...output track
status
SWA2...auto switch
SWOVT2...output tracking
switch
T3-2...output slew rate

Section 2. FCS Modules

AMS-2

2-47