If ANI0 is greater than or equal to ANI1, the following event sequence occurs as described in Table
3-5:

Table 3-5. High/Low Selector - ANI0

ANI1

Step

Module

Input(s)

Output(s)

Comments

1

ANI

ANI0 (C020) and
ANI1 (C021).

2

Math A

ANI0 (B123) and
ANI1 (B124).

L098 = 1

(True compare, ANI0 >
ANI1).

3

Logic A

B127 = 1 and
B128 = 1.

L097 = 0.

FC = 128 or A NOT;
therefore, two 1’s in =
a 0 out.

4

SP Gen 0

B149 = 0, which
enables setpoint
tracking (the 0 input is
inverted to a 1 within
the SP Gen 0 module
for setpoint tracking).
B148 = ANI0 value
(from step 1 output)
B150 = ANI1 value
(from step 1 output)
B151 is tied to a
steady 1 from L071,
which enables remote
setpoint.

C101 = ANI0
L104 = 1 to indicate
setpoint tracking is
selected.

Both setpoint tracking
and remote setpoint
are enabled, but the
selection priority in the
SP Gen 0 module is
always setpoint
tracking, remote
setpoint and the local
setpoint push buttons
last; therefore, setpoint
tracking (ANI0) is
selected.

5

Logic B

B130 = 1 and
B131 = 1.

L096 = 0, which
inhibits B142 of Param
D (ANI1 span).

FC = 128 or A NOT;
therefore, two 1’s in =
a 0 out.

6

Param C

B139 = L104 (1 from
step 4 output).
B140 = ANI0 span
value from datapoint
C006.

B141 = ANI0 span
value.

The ANI0 span value
is gated through the
Param C module to
datapoint C005.

7

Param D

B142 = L096 (0 from
step 5 output), which
inhibits Param D
output.

8

Datapoint
C005

C005 = B141 (from
step 6 output).

ANI0 span value.

9

Math B

B162 = C101 (ANI0
value from step 4 SP
Gen 0 output ).
B163 = ANI0 span
value from C005.

C031 = ANI0 value
augmented by the
Math B function code 4
algorithm.

10

ANO’s

B100 = C031, which is
the augmented ANI0
value.

ANO0 = B100 =
augmented ANI0 value.