MOD30ML and Modcell Maintenance Manual

DIAGNOSING I/O MODULE PROBLEMS

Table 5 .3. Analog Output Module Extended Error (EXTERR) Codes

Bit/Value

Status Display Message

Problem

Action

15 Unused

-----------------

-----------------

14/1

Read-back is zero

1. Incorrect connection to

module terminals

2. Module Error and Read

back Error

3. Fault in module or

Continuous error or
physical output errors

1. Verify

connections

(see IB-23C600)

2. Refer to the technical

note TNML1001-2.
See Appendix.

3. Replace

module

14/0

No message

Read-back is OK

None

13 Unused

-----------------

-----------------

12/1

Global error is indicated

An error has been detected

See error messages (bits

0-6)

12/0

No message

No error

None

11/1

Read-back is invalid

Fault in module

Replace module

11/0

No message

Read-back is OK

None

10/1

Read-back is out of range

Fault in module

Replace module

10/0

No message

Read-back is OK

None

9/1

In calibration mode

Status report

None

9/0

In standard mode

Status report

None

8 Unused

-----------------

-----------------

7/1*

Power-up or watchdog

timeout

1. Power-up

not

acknowledged

2. Acknowledge does not

clear power-up.

1. Acknowledge

power-

up

2. Replace

module

6/1*

Configuration checksum error

Fault in module

Replace module

5/1*

Host communications invalid

command error

Fault in module

Replace module

4/1*

EEPROM Calibration data

error

Fault in module

Replace module

3/1* EEPROM

communications

error

Fault in module

Replace module

2/1*

Host communications register

range error

Instrument trying to write to

unauthorized register

If error is repeated replace

module

1/1* Host

communications

checksum errors

Fault in module

Replace module

0/1*

Failsafe timeout

Fault in module

Replace module

*0 = No Error


5 -5