Register data – Micromod MOD: Modcell 2050R MODBUS Communications User Manual

Page 43

Advertising
background image

IB-23C650M

CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

CONTROLLER ATTRIBUTE LISTING - REGISTER DATA

The tables in this section provide a listing of the controller’s numeric attributes
which are addressed as registers. The tables divide the attributes into related
groups such as tuning, alarms, etc. A group of numeric attributes may have
associated boolean (discrete) attributes which are addressed as coils. The
boolean attributes are listed in the next section.

The following tables list the attributes in order by Modbus register number.
The letters below each number indicate whether the attribute is readable and
writeable or read only:

• R W

Readable and Writeable

• R _

Read only

Common Data (registers)

Reg.

#

Description

Register Value

2050R

Displayed Value

4

R W

Maximum milliseconds used in any
one cycle. This value is updated by
the controller and can be reset to zero
with a write by the host.

Typically written from
host as 0.

not displayed

5

R _

Average milliseconds used per cycle.
This should not exceed 250
milliseconds.

Number of
milliseconds

not displayed

6

R

_

Bits 15 - 4 indicate unacknowledged
process alarms (PA) and diagnostics
(DIAG).

Bit 15 = PA1
Bit 14 = PA2
Bit 13 = PA3
Bit 12 = PA4
Bit 11 = DIAG1
Bit 10 = DIAG2
Bit 9 = DIAG3
Bit 8 = DIAG4
Bit 7 = DIAG5
Bit 6 = DIAG6
Bit 6 = DIAG7
Bit 6 = DIAG8
Bits 0-3 Not Used

Refer to coil numbers 41-48 for
alarms and 49-64 for diagnostics.

39