Micromod MOD: Modcell 2050R 2050FZ0, QS-1300/1400 to 2050R Conversion Accessory User Manual

Micromod Equipment

Advertising
background image

Conversion Instructions for

QS-1300/1400 Conversion Accessory to MODCELL 2050

Accessory Part Numbers: 2050FZ00000A, 2050FZ00001A

INTRODUCTION

The MODCELL 2050 conversion accessory allows MODCELL 2050 to fit into an existing QS-1300 or QS-
1400 Slide-Guide installation. No external equipment such as instrument cables, power supplies or
termination panels are required. These instructions cover the procedure for the physical installation of
the QS-1300 conversion brackets onto a standard MODCELL 2050 housing, Slide-Guide installation and
limited electrical instructions.

Pages 3 through 10 include instructions for installation of the Direct Connect Cable when a
2050FZ00001A kit is being used. This feature provides the quickest installation while retaining the
original instrument cable. Ignore pages 3 through 10, if you are using the 2050FZ00000A conversion kit.

Parts Required:

2050FZ00000A or 2050FZ00001A Conversion Accessory

• metal brackets (3)

• 1/8" pop-rivets (6)

• Direct Connect Cable (1) [available in the 2050FZ00001A kit only]

MODCELL 2050 Single Loop Controller (1)

Tools Required: Pop-rivet

gun

PROCEDURE

Removal of the MODCELL 2050 instrument from the instrument housing is not required.

1. Remove the brackets and pop-rivets from the package. Be sure all parts are present.
2. Secure the three brackets to the MODCELL 2050 using the pop-rivet gun, and 1/8" pop-rivets

supplied in conversion the kit (see Figure 1). All six rivets are inserted through the bracket and
into the housing.

3. Remove the QS-1300/1400 instrument from the Slide-Guide. Insert the MODCELL 2050 in

place of the old instrument. MODCELL 2050 should latch in place like the QS-1300/1400
instrument did.

4. Connect wiring. When using kit number 2050FZ00000A, field I/O wiring for MODCELL 2050 may

be accomplished by cutting off the QS-1300 instrument connector and wiring directly to the
MODCELL 2050 termination block. See Table 1 for most common I/O configurations.

Figure 1. Mounting 2050R in Slide Guide

Advertising
Table of contents