Micromod MOD: Modcell 2050R 2050FZ0, QS-1300/1400 to 2050R Conversion Accessory User Manual
Page 7
Advertising
92902-88
2050F Conversion Instructions
2. This input configuration is for .25 - 1.25 Vdc where the controller supplies 24Vdc to the transmitter (2-
wire transmitter). If the controller does not supply power to the transmitter, the blue wire is not
required to be connected.
3. The controller must be equipped with a 2nd analog I/O option card.
Configuration Specifics:
The process input must be configured for volts in the "BASE CFG **MENU**". The process analog input
must be configured for .25 to 1.25 Vdc in the "INPUTS **MENU**". Both the control and retransmission
outputs must be configured for 4 - 20 mA in the "MA. OUTPT **MENU**".