5.2

Meter Board Connections (continued)

3.

External Switch Mechanism/In-Line Fuse Installation

To ensure a safe installation, the Class 4000/4100 requires an external

switch mechanism, such as a circuit breaker (max. 15 amps), be

installed to the Class 4000/4100 MAINS input wiring. The switch

mechanism must be installed in close proximity to the Class 4000/4100

and easily reachable for the operator. This device must also be marked

as the disconnecting device for the Class 4000/4100. Install 1/10 amp

Slow Activation inline fuses with the suitable voltage rating for

each conductor Phase at the MAINS input to the meter. The fuses must

be labeled to indicate voltage and current rating as well as element

characteristics. The fuse element must be slow activating type.

5.3

Current Sensor Installation & Wiring

The meter board contains two plug-in connectors located at the bottom center
of the board, TB2 and TB3. (See Figure 1.1.1) Connector TB2 is the input for
Phase A, and TB3 is the input for Phase B.

The Class 4000/4100 meter can be used with two types of current sensors:

1.

Split-core current sensor. This sensor opens so that it can be attached

around the circuit being monitored without interrupting power. Unless

otherwise

specifi ed, all Class 4000/4100 meters are supplied with this

sensor

type.

2.

Solid-core current sensor. This sensor does not open and requires the

monitored conductor to be removed from the circuit to install the current

sensor. This type is only supplied when specifi ed at time of order.

5.3.1

Installing the Split-Core Current Sensor Assembly

1.

Each phase being monitored will require one two-piece current sensor

assembly. Open the two-piece current sensor assembly by releasing

the nylon clamp using a fl athead screwdriver.

Page 7

2.0

Meter Technical Specifi cations

Ordering Information: Defi ne input voltage, current sensor rating and the RF
option, in the format C-xxx-yyyy-zz, where

C = number of conductors (2 or 3)

xxx=input voltage (120 or 208 [120/208/240])

yyy=current sensor rating (100, 200)

zz=designated option (W=none [Class 4000], WT (RF transceiver [Class 4100])

Example:

3 208 200 W

Number of conductors (3)

Input

Voltage

(208)

Current

Sensor

(200A)

RF

Transceiver

(none)

Input Voltage Confi guration

2-wire 120-volt, 3-wire 120/240-volt, 3-wire 120/208 volt

MAINS Voltage Input

Up to 240 VAC

Input Power

6 VA maximum rating

Current Sensor Rating

Up to 200 amps RMS AC available

Power Factor

0.5 leading or lagging

Line

Frequency

50-60

Hz

Metering

Accuracy

Certifi ed to ANSI C12.16 (+/-1% from 1-100% of rated load)

Voltage Operating Range

+/-10% of rated load

Temperature Range

-20 degrees C to +50 degrees C

Relative Humidity Range

0-95% non-condensing

Altitude

2000

meters

maximum

Voltage Overload

+25% continuously; +100% for 20 cycles

Current Sensor Overload

100% for 1 minute without damaging meter

Pollution Degree

Degree 2 in accordance with IEC 664

Installation (Overvoltage) Category

Category III

Measurement

Category

Category

III

Enclosure

Material

ABS

94VO

Display

Readout

6-digit

electro-mechanical

Standard Ranges

(2-wire)

120 VAC, 100, 200 Amp

(3-wire)

120/208/240

VAC,

100,

200

Amp

Modem

Interface

None

RS-485 Serial Communications

None

Load

Control

None

Recommended In-Line Fuse

Manufacturer: Littlefuse

Mfg Part No.: 313.100

Rating:

100mA, Slo-Blo, 250 VAC cartridge fuse

Table 2.0.1 Class 4000/4100 meter technical specifi cations.