3.0

Safety Label Defi nitions and Information

The Class 4000/4100 meter may contain one or more of the following labels.
Operator(s) should familiarize themselves with the meaning of each label to
minimize risk.

The presence of this label is a cautionary indicator

identifying a danger risk. The manual should be

consulted

prior

to

proceeding.

The presence of this label indicates an electrical

shock hazard exists in the location or area where

the label is placed. Prior to proceeding, the MAINS

power must be disconnected and the manual

consulted

for

safety

information.

4.0

Precautionary/Safety Information

WARNING:

High voltages present on main PCB terminal block TB1.

Risk of serious injury and/or electrical shock exists. Prior

to performing any wiring operations, review all contents of

the user manual and de-energize the MAINS power switch.

Only

qualifi ed personnel should perform installation

wiring. Installation wiring must comply with all local and

national

electrical

codes.

WARNING:

NEVER open front panel of unit while unit has MAINS

power applied. Failure to comply can increase the risk of

serious injury and/or electrical shock.

Page 5

5.0

Meter Installation

5.1

Mounting the Class 4000/4100 Meter

Use appropriately sized mounting hardware to fasten the Class 4000/4100
enclosure to the selected mounting surface. The four mounting holes are located
inside the enclosure and are accessed by removing the cover. The mounting
holes are centered 6 13/16” H x 4 13/16” W.

NOTE: Units must only be installed in indoor environments, where they will not

be affected by the elements.

5.2

Meter Board Connections

1. Wire

Entry:

Two 1/2” conduit openings are located on the back of the unit enclosure.

These openings are used for bringing in MAINS power and for current

sensor wiring. Route the appropriate cabling to and through the

respective enclosure opening.

After installing the conduit fi tting and conduit, verify that each conduit

slip nut is securely tightened to its respective conduit fi tting.

2.

Unit MAINS wiring:

The 4-position terminal block TB1, located at the bottom left corner of

the meter board, is clearly labeled A, B, C, N (neutral). AWG 14 or 12

gauge (stranded) conductors are typically utilized for this connection.

Figure 5.2.1.

Terminal

block

TB1.

A.

Connect the NEUTRAL wire to the appropriate terminal block position.

B.

On 2-wire, 120 VAC installations, connect the AC main power wire to the

Phase A position as labeled on terminal block TB1. On 3-wire 120/208

VAC installations connect the AC main power wires to Phase A and

Phase B positions on terminal block TB1. After all conductors are

connected to their respective terminal block positions and tightened

down, verify that each terminal block screw is securely fastened by

gently tugging on each conductor. Verify that no conductor wires

are frayed or shorting to adjacent terminal block positions.