Section 4 - Draft

Visit our website at: www.lanair.com

15a

9570 By-Pass
Regulator
(included)

8398 Vacuum Guage (included)

9807 Primary Strainer

(included)

1/2” Copper Tube
(to Burner - not included)

8662 Check Valve
(included)

(included)

8748 Strainer Suction Line

PUMP

ASSEMBLY
(included)

PUMP

ASSEMBLY
(included)

1/2” Copper Tube
(to Burner - not included)

Bottom of strainer must be 6”
from the bottom of the tank

Tank Drain Plug

1/2” Pick-up Tube

(not included)

TOP VIEW

Figure 3

The Lanair heater should have a (negative) -.02 draft reading when cold, and a (negative) -.06
when hot. Check the heater when it is running after 45 minutes. If the reading is not what it
should be, adjust the barometric damper according to the instructions provided with the
damper. The draft reading should be taken with a manometer. Consult your heating contrac-
tor, or a manometer can be purchased from the Lanair Customer Service Department .

Section 5 - Fuel Supply Tank Install w/ Bypass Regulator

If using a Lanair supply tank follow instructions included with the tank.

!