Ransburg, Air heater requirements – Ransburg RMA Indirect A11600 User Manual

Page 30

Advertising
background image

Figure 4: A11065-05 Air Heater

AIR HEATER

REQUIREMENTS

Turbine drive air expands as it moves through the

turbine wheel cavity and as it exits the turbine from

the exhaust port. This expansion will cause cool-

ing of the exhaust air and the surfaces it contacts.

This same expansion cooling can occur across

the shaping air exit ports. This cooling effect can

cause surface temperatures to fall below the dew

point of the booth, which will result in condensa-

tion on the interior and exterior of the atomizer,

machine, and its components. It is even possible

that the temperature of the supply air may be be-

low the booth dew point, even without additional

expansion cooling.

Condensation is especially probable in waterborne

applications when booth temperature and relative

humidity levels are typically maintained very high.

This condensation will allow sufficient conductivity

of the surfaces such that they act as an erratic

ground source potential. This can cause damage

to the equipment.

It is therefore, a requirement that turbine exhaust

air temperature be maintained above the booth

dew point to prevent condensation from forming

on atomizer surfaces. Doing so will eliminate

moisture as a potential defect in painted surfaces

as well as extending equipment life. Thus, it is

recommended that air heaters be installed into

the atomizer air supply lines, i.e. turbine drive air,

shaping air, and seal air. The air heaters must

be of sufficient capacity, capable of raising the

incoming air temperature at least 40°F (4.4°C) at

a flow rate of 60 SCFM per applicator.

The actual air heater process setting depends on

applicator fluid flow rate load, booth conditions,

turbine airflow settings, and incoming air tempera-

ture. The heater should be set as low as possi-

ble, sufficient to maintain the applicator surface

temperatures above the dew point in the booth.

Example: With the incoming air temperature at

72°F (22.2°C), an RMA-303 with 65mm bell cup

rotating unloaded at 60 krpm has a turbine outlet

temperature drop of approximately 28°F (-2.2°C)

(@ 40 krpm unloaded, ∆T ~ 14°F (-10°C)). Re-

ferring to the ASHRAE Psychrometric chart, the

saturation temperature range (dew point) of a

spray booth maintained at 70-75°F / 65-70%

RH is 62-68°F (21.1-23.9°C / 65-70° RH is 16.7-

20°C). Thus it is almost certain that the surface

temperatures of the applicator will fall below the

dew point of the booth, and an air heater will be

needed in this case.

To prevent condensation, an air heater assembly

(A11065-05) should be assembled after the air

filters. (Reference the current Air Heater Assembly

service manual for further information.)

> Failure to use an air heater may cause

damage to equipment or ruin the finished

component being processed.

NOTE

> Connect Air heater to turbine air tubing.

NOTE

RMA-303 Indirect Charge - Installation

Ransburg

26

LN-9252-06.4

Advertising