9060 cascade low voltage controller - installation – Ransburg 9060 LV Cascade Controller 80120-XXX User Manual

Page 25

Advertising
background image

9060 Cascade Low Voltage Controller - Installation

CP-13-02.3

20

For installations where it is required to run the
AC input wiring in conduit, perform the follow-
ing:

1. Ensure the AC line cord is unplugged

and remove the AC inlet receptacle wiring
from TB1-N, TB1-L1 and TB1-EARTH
GROUND (See Figures 8 and 9).

2. Remove the mounting hardware from the

AC inlet receptacle and remove it from the
side of Controller.

3. Install the Conduit Adapter Plate (See

Accessories Section) in the hole where the
AC inlet receptacle was removed (see
Figure 10).

4. Install the AC input wiring (0.8mm

2

(18AWG) minimum) through the Conduit
Adapter Plate using conduit and wire to TB1

In general, conduit must be used for

approved AC installation, however, if na-
tional and local codes permit, the AC
power may be supplied via the factory
supplied line cord. If conduit is utilized,
the Controller AC input wiring may be
routed through an optional explosion
proof switch mounted on or near the
spray booth where it will be convenient to
the operator.

N O T E

Hot/Line

to TB1-L1

Neutral/Common to TB1-N

Ground

to TB1-EARTH GROUND

Figure 8: Location of TB1 in Controller

Figure 9: TB1 Interlock Wiring

Figure 10: Installation of Conduit Adapter Plate

TB1

Back of Cabinet

Conduit
Adapter Plate

SIDE VIEW