9060 cascade low voltage controller - operation – Ransburg 9060 LV Cascade Controller 80120-XXX User Manual

Page 47

Advertising
background image

9060 Cascade Low Voltage Controller - Operation

CP-13-02.3

42

Over Voltage Fault (OU)

This fault will occur if the microprocessor de-
tects the unit is trying to output voltage above
the required for the specific applicator type. If
this occurs, reset the Controller. If this fault
continues to occur, replace the main PC
board.

Figure 40: Over Voltage Fault Display

Feedback Fault (FF)

This fault will occur if the microprocessor de-
tects a loss of the current feedback signal. If
this occurs, reset the fault. If this fault occurs
repeatedly, replace the external cascade or
send the high voltage controller in for repair.

Figure 41: Feedback Fault Display

DI/DT Overload Fault (dOL)

This fault is ONLY applicable to 80100-51X
units.

This fault will occur if the microproces-

sor detects that the rate of current change has
exceeded the limits specified in the user DI/DT
settings. If this occurs, reset the fault. Check
to ensure that no object is moving toward the
applicator within the minimum safe distance,
adjust the DI/DT settings if necessary, and re-
test operation. If this fault continues to occur,
contact your Ransburg Representative.

Figure 42: DI/DT Overload Fault Display