Robertshaw 9515 User Manual

Page 7

Advertising
background image

7

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR
SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND
VOID YOUR WARRANTY.

CAUTION: D

O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW

50°F (10°C).

T

HIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY

.

1. Place the COOL-OFF-HEAT

switch into the COOL position.

2. Press the

button until the

temperature setting is at least
3 degrees below the room
temperature. The air conditioning
system should turn on within
a few seconds.

NOTE: When in the COOL mode once the thermostat turns off, a built in 5-
minute delay prevents the system from turning on again. This protects the
compressor. No additional time delay relay is required. To override the 5-
minute delay for installation, press the RESET button.

3. Put the COOL-OFF-HEAT switch

into the OFF position. The air
conditioning system should turn off.

4. Put the COOL-OFF-HEAT switch

into the HEAT position.

5. Press the

button until the

temperature setting is at least
3 degrees above room temperature.
The heating system should turn on.
The fan may not turn on immediately,
depending upon the fan delay built
into the furnace.

6. Put the COOL-OFF-HEAT switch

into the OFF position. The heating
system should turn off. The fan may
continue to run for a short period
of time.

7. Put the

AUTO-ON switch to the

ON position. The blower fan should
turn on.

8. Put the

AUTO-ON switch to

the AUTO position. The blower fan
should turn off.

COOL-OFF-HEAT

COOL-OFF-HEAT

COOL-OFF-HEAT

>

AUTO - ON

>

COOL-OFF-HEAT

AUTO - ON