Rev 2.0 : X11CA-IM MASTER MODULE

3

2 X11-MF3 FIRMWARE

The firmware on the X11CA-IM scans each X11CA alarm module for the following
information.

Field contacts (A, B, C, D),
H1 (Horn1), H2 (Horn2) and CTA (Common Trouble Alarm),
Operation mode for each channel (IA, IB, IC, ID),
First Out indication for each channel (FA, FB, FC, FD)


The scanned information is then stored into the holding registers, starting at the address
00, in two byte format as shown below.


Hi byte

FD

FC

FB

FA

ID

IC

IB

IA

Low byte

S

H2

H1 CTA

D

C

B

A



The following list has the descriptions of each data bit.

Descriptions

A

Status of the first input

B

Status of the second input

C

Status of the third input

D

Status of the forth input

CTA

Status of Common Trouble Alarm

H1

Status of the Horn1

H2

Status of the Horn2

S

Communication status bit: 0=Successful, 1=Failed to communicate with
X11CA Alarm modules.

IA

Operation mode of Channel A. If IA=0, CH A is Contact Input.
If IA=1, CH A is serial input.

IB

Operation mode of Channel B. If IB=0, CH B is Contact Input.
If IB=1, CH B is serial input.

IC

Operation mode of Channel C. If IC=0, CH C is Contact Input.
If IC=1, CH C is serial input.

ID

Operation mode of Channel D. If ID=0, CH D is Contact Input.
If ID=1, CH D is serial input.

FA

If FA=1, CH A is the First Out channel within the group.

FB

If FB=1, CH B is the First Out channel within the group.

FC

If FC=1, CH C is the First Out channel within the group.

FD

If FD=1, CH D is the First Out channel within the group.

Table 2-1 Descriptions of Modbus Communication Data Format